Connection with coaxial pipes
fig. 12 - Examples of connection with coaxial pipes (
Table. 2 - Typology
Type
Description
C1X
Wall horizontal exhaust and inlet
C3X
Roof vertical exhaust and inlet
For coaxial connection, fit the unit with one of the following starting accessories. For the
wall hole dimensions, refer to fig. 25. Any horizontal sections of the fume exhaust must
be kept sloping slightly towards the boiler, to prevent possible condensate from flowing
back towards the outside and causing dripping.
Ø 100
Ø 60
041002X0
041001X0
fig. 13 - Starting accessory for coaxial ducts
Table. 3 - Baffle for coaxial pipes for model DIVACONDENS F24 D
Max. permissible length
Reduction factor 90° bend
Reduction factor 45° bend
Baffle to use
Table. 4 - Baffle for coaxial pipes for model DIVACONDENS F28 D
Max. permissible length
Reduction factor 90° bend
Reduction factor 45° bend
Baffle to use
= Air /
= Fumes)
Ø 127
Ø 80
041006X0
Coaxial 60/100
Coaxial 80/125
6 m
12 m
1 m
0.5 m
0.5 m
0.25 m
0 ÷ 2 m
Ø 45
0 ÷ 6 m
2 ÷ 4 m
Ø 50
6 ÷ 12 m
4 ÷ 6 m
no baffle
Coaxial 60/100
Coaxial 80/125
4 m
12 m
1 m
0.5 m
0.5 m
0.25 m
0 ÷ 2 m
Ø 50
0 ÷ 6 m
2 ÷ 4 m
no baffle
6 ÷ 12 m
cod. 3541N242 - Rev. 02 - 04/2018
Connection with separate pipes
C
5x
fig. 14 - Examples of connection with separate pipes (
Table. 5 - Typology
Type
Description
C1X
Wall horizontal exhaust and intake. The inlet/outlet terminals must be concentric or close enough to be
undergo similar wind conditions (within 50 cm)
C3X
Roof vertical exhaust and intake. Inlet/outlet terminals like for C12
C5X
Wall or roof exhaust and intake separate or in any case in areas with different pressures. The exhaust
and intake must not be positioned on opposite walls.
C6X
Intake and exhaust with separately certified pipes (EN 1856/1)
B2X
Intake from installation room and wall or roof exhaust
IMPORTANT - THE ROOM MUST BE PROVIDED WITH APPROPRIATE VENTILATION
For the connection of separate ducts, fit the unit with the following starting accessories:
fig. 15 - Starting accessory for separate ducts
cod. 041039X0
cod. 3900C110
Before installation, make sure the maximum permissible length has not been exceeded,
by means of a simple calculation:
1.
Establish the layout of the system of split flues, including accessories and outlet ter-
minals.
2.
Consult table 8 and identify the losses in m
nent, according to the installation position.
3.
Check that the sum total of losses is less than or equal to the maximum permissible
length in table 6.
Ø 45
no baffle
Table. 6 - Baffles for separate ducts DIVACONDENS F24 D
Max. permissible length
Baffle to use
Ø 50
Table. 7 - Baffles for separate ducts DIVACONDENS F28 D
no baffle
Max. permissible length
Baffle to use
B
2x
= Air /
Ø 81
Ø 81
041039X0
(equivalent meters) of every compo-
eq
Separate ducts
60 m
eq
0 - 20 m
eq
20 - 45 m
eq
45 - 60 m
eq
Separate ducts
55 m
eq
0 - 35 m
eq
35 ÷ 55 m
eq
EN
C
1x
= Fumes)
Ø 45
Ø 50
No baffle
Ø 50
No baffle
55