Configuration Menu

The configuration Menu is accessed by pressing the DHW buttons together for 10 sec-
onds. 12 parameters, indicated by the letter "b" and not modifiable from Remote Timer
Control, are available.
Press the Heating buttons to scroll the list of parameters in increasing or decreasing or-
der. Press the DHW buttons to view or modify the value of a parameter: the change will
be automatically saved.
Contents Description
b01
Gas type selection
b02
Boiler type selection
Combustion chamber type selec-
b03
tion
b04
Primary Exchanger type selection 0 ÷ 13
Variable output relay operation
selection (b02=1)
b05
No effect on adjustment (b02=2)
No effect on adjustment (b02=3)
No effect on adjustment (b02=4)
b06
Mains Voltage Frequency
Comfort burner on time
(b02=1)
No effect on adjustment (b02=2)
b07
No effect on adjustment (b02=3)
No effect on adjustment (b02=4)
b08
Gas valve driver
b09
DHW demand type selection
Flowmeter timing (b02=1)
Flowmeter timing (b02=2)
b10
No effect on adjustment (b02=3)
No effect on adjustment (b02=4)
DHW mode activation flow rate
(b02=1)
DHW mode activation flow rate
b11
(b02=2)
No effect on adjustment (b02=3)
No effect on adjustment (b02=4)
b12
Enable Auto-Settings procedure
Notes:
1.
Parameters with more than one description vary their function and/or range in rela-
tion to the setting of the parameter given in brackets.
2.
Parameters with more than one description are reset to the default value if the pa-
rameter given in brackets is modified.
To exit the configuration Menu press the DHW buttons together for 10 seconds, or exiting
occurs automatically after 2 minutes.
58
EN
Range
Parameter
0=Natural Gas
0
1=LPG
1=Bithermal instantaneous
2=Monothermal instantaneous
2
3=Heating only (3-way valve)
4=Heating only (circulating pump)
0=Sealed Chamber combustion control
(without fume pressure switch)
1=Open Chamber (with fume thermostat)
2=Sealed Chamber (with fume pressure
switch)
3=Sealed Chamber Combustion control
3
(with fume thermostat on recuperator)
4=LOW NOx Sealed Chamber Combustion
control
(without fume pressure switch)
5=LOW NOx Open Chamber
(with fume thermostat)
8 (for model F24 D)
9 (for model F28 D)
0 = External gas valve
1 = System filling solenoid valve
2 = Solar 3-way valve
3 = Supply indicator with fault present
4 = Supply indicator without fault present
5 = External circulating pump (during demand
and post circulation)
--
0
--
--
0=50Hz
0
1=60Hz
0-20 seconds
--
5
--
--
0 = Standard, 1
0
0 = Flow switch
1 = Flowmeter (190 imp/l)
1
2 = Flowmeter (450 imp/l)
3 = Flowmeter (700 imp/l)
0 = Deactivated
1 ÷ 10=seconds
0=Deactivated
0
1-10=seconds
--
--
10 ÷ 100 L/min/10
10 ÷ 100 L/min/10
15
--
--
0 = Disabled
0
1 = Enabled
cod. 3541N242 - Rev. 02 - 04/2018
DIVACONDENS F D

Service menu

The card Service Menu is accessed by pressing the Reset button for 20 seconds. 4 sub-
menus are available: press the Heating buttons to select, in increasing or decreasing or-
der, "tS", "In", "Hi" or "rE". "tS" means Transparent Parameters Menu, "In" means
Information Menu, "Hi" means History Menu: after selecting the submenu, press the Re-
set button again to access it; "rE" means History Menu Reset: see description.
"tS" - Transparent Parameters Menu
21 parameters indicated by the letter "P" are available, which are also modifiable from
Remote Timer Control.
Press the Heating buttons to scroll the list of parameters in increasing or decreasing or-
der. Press the DHW buttons to view or modify the value of a parameter: the change will
be automatically saved.
Contents Description
P01
Ignition ramp Offset
P02
Heating ramp
P03
Heating standby time
P04
Heating Post-Circulation
P05
Heating user max. set point
P06
Max. output in heating
Burner shutdown in DHW (b02=1)
P07
Burner shutdown in DHW (b02=2)
Hot water tank hysteresis (b02=3)
Hot water tank hysteresis (b02=4)
DHW standby time (b02=1)
DHW standby time (b02=2)
P08
DHW standby time (b02=3)
DHW standby time (b02=4)
DHW user max. set point (b02=1)
DHW user max. set point (b02=2)
P09
DHW user max. set point (b02=3)
DHW user max. set point (b02=4)
Anti-inertia function temperature
(b02=1)
No effect on adjustment (b02=2)
P10
Delivery temperature in DHW (b02=3) 70-85°C
Delivery temperature in DHW (b02=4) 70-85°C
Anti-inertia function Post-Circulation
(b02=1)
DHW Post-Circulation (b02=2)
P11
DHW Post-Circulation (b02=3)
DHW Post-Circulation (b02=4)
P12
Max. output in DHW
P13
Absolute min. power
P14
Post-Ventilation
CO2 limit Offset (b03=0)
No effect on adjustment (b03=1)
No effect on adjustment (b03=2)
P15
CO2 limit Offset (b03=3)
CO2 limit Offset (b03=4)
No effect on adjustment (b03=5)
P16
Exchanger protection activation
Modulating pump max. speed - abso-
P17
lute
Modulating pump max. speed - post
P18
circulation
Range
DIVACONDENS F D
0-40
20
1-20°C/minute
5
0-10 minutes
2
0-20 minutes
6
31-85°C
80
0-100%
100
0=Fixed
1=Linked to set point
2=Solar
3 = DO NOT USE
4 = DO NOT USE
0=Fixed
1=Linked to set point
2=Solar
0
3 = DO NOT USE
4 = DO NOT USE
0 (do not use) 1-2-3-4°C
0 (do not use) 1-2-3-4°C
0-60 seconds
0-60 seconds
30
0-60 seconds
0-60 seconds
50-65°C
50-65°C
50
50-65°C
50-65°C
5-85°C
--
0
0-10 Seconds
0-60 Seconds
30
0-60 Seconds
0-60 Seconds
0-100%
100
0-100%
0
0=Default
0
1=50 seconds
0 (Minimum)
30 (Maximum)
--
--
0 (Minimum)
20
30 (Maximum)
0 (Minimum)
30 (Maximum)
--
0=No F43
10
1-15=1-15°C/second
0-100% not working.Always at 100% in
100
this model
0-100% not working.Always at 100% in
60
this model