RIB KS2 Manual Del Usuario página 20

Cuadro electrónico de mando para uno o dos motores monofásicos
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

G
B
stops M1 (with storage of the encoder readings and the time) and the
delay countdown priot to automatic closing starts (max 5 minutes).
5 - Press PROG. => delay countdown prior to automatic closing stops and
M2 closes. At the same time LED DL9 stops blinking to signal exit from
the programming mode. At this point, the safety devices and other gate
controls will resume normal operation (inversions, stops, alarms, etc.).
6 - The gate will stop at the end of the ENCODER countdown.
7 - AFTER PROGRAMMING, SWITCH DIP 2 TO OFF.
NOTE: The same procedure applies to electric limit switches (S3 closed).
With S3 closed, gate travel is determined by the electric limit switches
and not by the encoder, which only acts as a safety device.
MODE 4
1 - Start with the gate completely closed.
2 - Put DIP 2 in the ON mode => LED DL9 will blink rapidly.
3 - Press PROG. => M1 opens.
4 - When the gate comes into contact with the opening stop, wait one second
then press PROG. => M1 stops and the delay countdown prior to
automatic closing starts (max 5 minutes).
5 - Press PROG. => delay countdown prior to automatic closing stops and
M1 closes. At the same time LED DL9 stops blinking to signal exit from
the programming mode. At this point, the safety devices and other gate
controls will resume normal operation (inversions, stops, alarms, etc.).
6 - The gate will stop at the end of the ENCODER countdown.
7 - AFTER PROGRAMMING, SWITCH DIP 2 TO OFF.
O
PERATION OF THE OPERATING ACCESSORIES
OPENING BUTTON (with timer function)
When the gate is standstill, the button operates the opening mode. If you
push this button when the gate is on closure, It opens again.
TIMER FUNCTION
This function is useful In the rush hours, when vehicle traffic is slow (e.g.
entry/exit of workers, emergencies In residential or parking areas and,
temporary, for removals).
APPLICATIONS
By connecting a switch and/or a daily/weekly timer (in place or in parallel with
the opening button N.O. "COM-OPEN"), it is possible to open the automation
or to keep It open, as long as the switch is on or the timer is activated.
When the automation is open, all operating functions are inhibited.
If the automatic closing Is started, by releasing the switch or at the time set
before, the automation immediately closes; if not, you need to operate a
command.
CLOSING BUTTON (COM-CLOSE)
When the gate Is standstill, It operates the closing.
JOGGING OPERATION BUTTON (COM-K BUTTON)
DIP5 - OFF => It cyclically commands open-stop-close-stop-open-etc.
DIP5 - ON => It opens the gate when this Is closed. If It Is operated while
the gate Is opening, It has no effect. If It Is operated when the
gate is open, it closes the gate and, If It Is operated while the
gate Is closing, It opens the gate again.
RADIO TRANSMITTER
DIP4 - OFF => It cyclically commands open-stop-close-stop-open-etc.
DIP4 - ON => It opens the gate when this is closed. If It Is operated while the
gate Is opening, It has no effect. If It Is operated when the gate
Is open, It closes. If It Is operated while the gate Is closing, It
opens the gate again.
AUTOMATIC CLOSING
Pause times before the automatic closing of the gate are set with the timing
procedure.The maximum pause time is 5 minutes.
Pause time can be started or stopped by DIP3 (ON started).
ELECTRIC LOCK IN OPENING PHASE
Set DIP10 to ON to enable control of the electric lock in the opening phase.
ELECTRIC LOCK AND RELEASE PULSE IN OPENING PHASE
Set DIP11 to ON to enable the release pulse of the electric lock in the
opening phase (provided S2 DIP10 is set to ON).
With the gate closed, pressing an opening command will cause the gate to
perform the closing movement for 0.5s (in this phase the Encoder(s) is/are
not enabled), and simultaneously the electric lock is activated (followed by
0.5s pause and then by opening of the gate).
GATE LEAF RELEASE ASSIST:
With the electric lock release pulse active (DIP11 - ON), when the gate is
closed a direction reversal manoeuvre is performed for a fixed time of 0.2s to
facilitate manual release (in this phase the Encoder is not enabled).
OPERATION AFTER BLACK-OUT
When mains electrical power is restored press the opening button (K, OPEN,
radio).
The gate will open. Let the gate close itself with automatic closure or wait that
the flasher stops blink first to command the closing movement. This operation
is valid to obtain the leaves position readjustment. During this phase all
safety devices are active.
(#) SAFETY DEVICES ARE ACTIVE DURING THE PROGRAMMING AND
THEIR INTERVENTION STOPS IT (THE LED 9 BLINKS NO MORE BUT
REMAINS CONSTANTLY TURNED ON).
TO REPEAT THE PROGRAMMING, POSITION DIP1 AND 2 ON MODE
OFF, CLOSE THE GATE AND REPEAT THE PROCEDURE DESCRIBED
ABOVE.
S
AFETY ACCESSORIES OPERATION
SAFETY ENCODER
It serves as a safety device both during opening and on closure, with
movement reversion.
DIP 7 (ON) OPERATES THE MOTOR WITH ENCODER.
If the Encoder does not work (due to a failure In the power supply,
disconnected wires, broken or defective disk), the gate Is not operated.
If the encoder operates the closing or the opening and than gives a reverse
command, the gate stops and reverses Its movement for 1 second. The
buzzer buzzes to alarm for 5 minutes and the blinker blinks for 1 minute.
During or after the 5 minutes, when the buzzer alarms, you can make the
gate work again just pressing the operating button you want.
PHOTOCELL 1 (COM-PHOT 1)
If DIP 6 is OFF => The gate does not open if there is an obstacle within the
photocells range of action. During operation, photocells
work both when the gate opens (by starting the opening
movement again after half a second time), and when
it closes (by starting the reverse movement after one
second time).
If DIP 6 is ON => If there is an obstacle within the photocells range of action
when the gate is closed and its opening is commanded,
the gate opens (during Its opening, photocells do not
work). Photocells work only while the gate Is closing (by
starting Its reverse motion after one second, even if they
are still engaged).
N.B.: Every six months make sure to check that photocells are not out
of order
STOP BUTTON
The STOP button stops the gate during any operation.
If you push it when the gate is totally open (or partly open, by using the
pedestrian command), this button temporary excludes the automatic closing
(if selected by DIP3). It Is than necessary to operate another command to
make the gate close again.
The automatic closing function Is enabled again with the following operating
cycle (if selected by DIP3).
BLINKER
N.B.: This electric board can supply power ONLY TO BLINKERS WITH
BLINKING CIRCUIT (ACG7059), with max. 40W lamps.
20
20

Publicidad

Tabla de contenido
loading

Tabla de contenido