Friwa
2.4
Circulation option (thermostat variant)
Control of circulating pump (thermostatic)
Within a given time frame (timer WT), the temperature of
the hot water pipe is monitored using the T-C sensor. If this
temperature falls below the adjusted minimum temperature
(Circ. min), the circulating pump is activated. It is switched
off when the temperature of the hot water in the pipe has
increased by the heating hysteresis (Circ. hyst.).
P1
loading pump
Pc
circulating pump (optional)
T-HW
sensor - hot water temperature
Main manu:
Meas. values
Reports
Balances
Settings
Options
Manual operation
User code
Expert
T- HW
T- S
T- CW (S7)
P1
T-CW
sensor - cold water temperature
T-S
sensor - heat source temperature
dV
fl ow rate - measuring instrument
--> 1. Options
Options
Parameter
Range
Circulat.
No/Dem./Therm.
default is No
--> 2. Adjustment values
Settings
Parameter
Range
CirC. Sensor S5/S6/S7,
default is S7
Ciric.-Hyst.
0,5..10,0 K,
default is 5,0 K
Circ.-Min.
10..60° C,
default is 40° C
Week Timer Circ. 00:00..23:59,
default is Mo-Su,
On-Off 05:00-08:00,
11:00-14:00, 18:00-21:00
--> 3. Measured values
Meas. values
Parameter
Range
T-C
-50 ... 250 °C
Circulation
Off ... On
--> 4. Check function
The active function will be shown on the display.
Sensor T-C can either be combined with a sensor at S5, S6 or
with sensor S7 (factory setting T-CW).
Pc
S8
dV
Description
thermostatic
thermostatic control of circulating pump
Description
sensor selection - circulation return
heating hysteresis - circulation
minimum temperature - circulation
weekly timer - circulation
adjust the desired operating time of the
circulating pump
Description
temperature - circulation return
status of circualting pump
optional
S5 or S6
optional
circulation
cold water
23
|