Overview Of Functions And Options - PAW Friwa Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Friwa
4.

Overview of functions and options

Menu
Temperature - domestic hot water
T-Hw
Temperature - cold water
t-Cw
Temperature - heat source
t-S
Temperature - return
t-r
Temperature - store
t-st
Temperature - circulation
t-C
Flowrate
Tap
Speed - loading pump
Load. Pump
Status - circulating pump
Circulation
Status - return connection
Return Valve
Operating mode R1-R5
Relay 1-5
Sensors 1-9
Sen. 1-9
Status - manual operation function
-Manual Oper.
Circulating time
Circ. Run
Circulating break time
Circ. Wait
Heat up hysteresis - cirulation
Circ. Hyst.
Minimum temperature - circulation
CirC. Min
Weekly timer - circulation
Week Timer circ.
Circulation option
Circualt.
Status - circualtion function
-Circulation
Return - connection option
Return Div.
Switch-on difference - return valve
DT-rd on
Switch-off difference - return valve
Dt-Rd Off
Status - return connection
-Return Div.
Error relay option
Error. Rel.
Operating relay option
Signal Rel.
External shutdown option
extern off
Status - hot water generation function
-Hot Water Gen.
Operating days - controller
Operation
Draw off quantity
Volume
Maximum flow rate
vol. max
Operating hours - loading pump
Load. Pump
Operating hours - circulating pump
Circ.-p.
Minimum temperature source
t-S min
Maximum temperature source
t-S max
Minimum temperature - cold water
t-Cw mn
Maximum temperature - cold water
t-Cw mx
Energy - hot water
Heat qtY
Emergency operation option
Emergency
Emergency operation pump speed
Emergency
Status - emergency operation
-Emergency
Operat.
Error message - sensor
!Sensor Failure
30
|
Description
Type
Range
M
-50,0 ... 250,0 °C
M
-50,0 ... 250,0 °C
M
-50,0 ... 250,0 °C
M
-50,0 ... 250,0 °C
M
-50,0 ... 250,0 °C
M
-50,0 ... 250,0 °C
M
0 ... 9999 l/h
M
Off / 0 ... 100 %
M
Off ... On
M
Off ... On
P
On / Auto / Off
M
-50,0 ... 250,0 °C
S
P
1 Min. .. 10 Min.
P
0 Min. .. 20 Min.
P
0,5 ... 10 K
P
10 ... 60 °C
P
Mo. 00:00 ...So. 23:59
P
No/Demand/Therm.
S
P
yes ... no
P
0,0 ... 25,0 K
P
0,0 ... 25,0 K
M
P
no ... R4/R5
P
no ... R4/R5
P
yes ... no
S
B
0 ... 99999 Tg.
B
0,0 ... 9999,9 m3
B
0 ... 9999 l/h
B
0 ... 99999 h
B
0 ... 99999 h
B
-50,0 ... 250,0 °C
B
-50,0 ... 250,0 °C
B
-50,0 ... 250,0 °C
B
-50,0 ... 250,0 °C
B
0 ... 999
P
yes ... no
P
12 ... 100 %
S
S
Factory setting
Page
-----
21
-----
21
-----
21
-----
24
-----
24
-----
23
-----
21
-----
21
-----
21
-----
24
Auto
25
29
-----
29
2 Min.
22
10 Min.
22
5,0 K
23
40 °C
23
23
no
21
-----
29
no
21
5,0
24
3,0
24
29
no
21
no
21
no
21
-----
29
0
25
0,0
25
0
25
0
25
0
25
250,0 °C
25
-50,0 °C
25
250,0 °C
25
-50,0 °C
25
Wh/kWh/MWh
25
no
21
100 %
25
-----
29
29

Publicidad

Tabla de contenido
loading

Tabla de contenido