Return connection option

Return connection
During low demand or circulation, high return temperatures
can be generated. These can be fed to the buffer store at
a higher temperature level using the 3 port valve. This will
avoid mixing with the lower cooler zone.
When the difference between return temperature (T-R) and
store reference temperature (T-St) exceeds the adjusted
switch-on difference (dT-Rd on), relay RC is energised.
T- St
VR
P1
loading pump
Pc
circulating pump (optional)
T-HW
sensor - hot water temperature
Main menu:
Meas. values
Reports
Balances
Settings
Options
Manual operation
User code
Expert
24
|
T- S
P1
T- R
--> 1. Options
Options
Parameter
Return Div.
--> 2. Adjustment values
Settings
Parameter
DT-Rd on
DT-Rd off
--> 3. Measured values
Meas. Vaules
Parameter
T-St
T-R
Return valve Off/On
--> 4. Check function
It is deactivated when the loading circuit is not operated
or when the difference falls below the adjusted switch-off
difference (dT-Rd off).
T- HW
dV
T- CW
T-CW
sensor - cold water temperature
T-S
sensor - heat source temperature
dV
fl ow rate - measuring instrument
Range
Description
On
Off/On,
default is Off
Range
Description
switch-on difference - return valve
0,0 ... 25,0 K,
default is 5,0 K
switch-off difference - return valve
0,5 ... 10,0 K,
default is 5,0 K
Range
Description
store temperature
-50 ... 250 °C
return temperature
-50 ... 250 °C
status of return connection valve (RC)