Technical data - Buffer module CP-B 24/10.0
o
Data at T a = 25
C and rated values, unless otherwise indicated
Type
Input circuit - Supply circuit
Rated input voltage U in
Input voltage range
Min. charging potential
Rated input current
Inrush current limiting
Transient overvoltage protection
Internal input fuse (apparatus protection), not accessible
Internal fuse capacitor circuit (not acessible)
Kind of input
Output circuit
Rated output power
Rated output voltage U out
Output voltage (buffer mode)
Tolerance of the output voltage
Rated output current I r
Peak output current
(fully loaded capacitors required)
Control of limiting current
Shut-down if limiting current is exceeded
Short-circuit protection
(via internal 15 A fuse and external 10 A fuse)
Internal output fuse (not accessible)
Required external fuse
Current limiting at output circuit
Breaking capacity of output circuit
Power failure buffering time
Overload protection
Kind of output
Contact material
Min. switching voltage / min. switching current
Max. switching voltage / max. switching current
Mechanical lifetime
Electrical lifetime
Max. fuse rating to achieve short-circuit
protection
SHUT-DOWN
Rated voltage
Voltage range
T a < 60 °C
T a < 60 °C
= 2.5 ms
INPUT OK
BUFFER STATUS
FAILURE
n/o or n/c contact
CP-B 24/10.0
L+
, L-
IN
IN
24 V DC
23.9-27.0 V DC
23.9 V DC
10 A DC
35 A / 2 ms
varistor / suppressor diode
15 A (FK2)
25 A (FK2)
control input
24 V DC
6-45 V DC
L+
, L-
, L-
OUT
OUT
240 W
24 V DC
23.2 V DC
+2...-10 %
10 A DC
20 A DC (min. 1.5 s)
(10 A power supply unit + 10 A buffer module)
10.3 A DC ±0.1 A
after 1.5 s
no continuous short-circuit stability
15 A (FK2)
10 A slow-acting
1.05-1.2 x I r
24 V DC, 10 A
load-dependent, min. 38 s at 100 % load
thermal protection
n/o contact
n/o contact
c/o contact
Ag + Au-clad
5 V DC / 1 mA
50 V AC / 1 A; 30 V DC / 0.5 A
6
5 x 10
switching cycles
6
0.1 x 10
switching cycles
1 A AC / 0.5 A DC
OUT
15