Table 10-1 Status indications
String
The drive is inhibited and cannot be run. The Drive Enable signal is not applied
inh
to the drive enable terminal or is set to 0.
The drive is ready to run. The drive enable is active, but the drive inverter is
rdy
not active because the final drive run is not active
StoP
The drive is stopped / holding zero speed.
S.Loss
Supply loss condition has been detected
dc inj
The drive is applying dc injection braking
The drive has tripped and no longer controlling the motor. The trip code
Er
appears on the display.
UV
The drive is in the under voltage state.
STEP 11: Understand key parameters and restoring default
When changing a parameter, the new value is saved when pressing the Enter button to return to parameter view
mode from parameter edit mode.
Restoring default parameters:
1.
Ensure the drive is not enabled, i.e. terminal 11 (or terminal 31 and 34 on Unidrive M300) is open.
2.
Select 'Def.50 (50 Hz settings) or Def.60 (60 Hz settings)' in Pr 00.
3.
Press the red reset button
Parameter
01
Minimum Speed
02
Maximum Speed
03
Acceleration Rate 1
04
Deceleration Rate 1
05
Drive Configuration
06
Motor Rated Current
07
Motor Rated Speed
08
Motor Rated Voltage
09
Motor Rated Power Factor
10
User Security Status
8
Description
Range ( )
0.00 to Pr 02 Hz
0.00 to 550.00 Hz
0.0 to 32000.0 s/100 Hz
0.0 to 32000.0 s/100 Hz
Refer to the Quick Start Guide for further
information on all drive configurations
0.00 to Drive Rating Amps
0.0 to 33000.0 rpm
0 to 240 V or 0 to 480 V
0.00 to 1.00
Refer to the Quick Start Guide for further
information
Unidrive M100/M101/M200/M201/M300 Step By Step Guide
Drive output
stage
Disabled
Disabled
Enabled
Enabled
Enabled
Disabled
Disabled
Default ( )
0.00 Hz
Def.50: 50.00 Hz
Def.60: 60.00 Hz
5.0 s/100 Hz
10.0 s/100 Hz
M100/M200/M300: AV
M101/M201: PAd
Maximum Heavy Duty
Rating Amps
Def.50: 1500.0 rpm
Def.60: 1800.0 rpm
110V drive: 230 V
200V drive: 230 V
400V drive Def.50: 400 V
400V drive Def.60: 460 V
0.85