During the installation and operation of the instrument, please proceed
as follows:
1) The instrument should be installed by a capable operator
2) Carefully follow the connection diagrams when installing the instrument
3) When connecting the instrument, always use TA x/5 A
4) The appliance should be installed in a panel in such a way that there is
no access to the terminals following installation
5) The terminals of the voltage and current circuits may be connected with
a maximum rated voltage to earth of 300 V eff
6) The panel should be wired in accordance with the EN standards
7) Do not power or connect the instrument if any part of it is damaged
NOTE:
The ORBIS power supply analysers are designed for use in areas with
over-voltage category III and pollution level 2, in line with the
EN 61010-1 standard
The electrical system of the building in which the instrument is to be
installed should be fitted with a disconnection or isolator switch, which
should be located near the instrument and be easy to reach.
An over-current protection device should be fitted.
ower supply: 115-230 V AC (-15%/+10%) - 50/60 Hz
140-300 V DC
Maximum power consumption: 4 VA
Display:
- 3x3 digit fields for the display of the phase values.
1x7 digit numerical field for the display of the active and reactive energy
and the system and total values.
- 8 indicator lamps for the value selected, the measurement unit and the
pre-set value, where applicable
oltmeter inputs: 500 V AC RMS (phase-phase), 47-63 Hz
Ammeter inputs: 6 A, 47-63 Hz
Scales: 1 voltage scale with maximum 500 V RMS
2 automatic selection current scales with maximum 2 A RMS and 6 A RMS
- Voltage: 0.5% of maximum reading (minimum signal that can be
measured 4% of maximum reading)
- Current: 0.5% of maximum reading (minimum signal that can be
measured 20 mA)