Comprobación de ajustes - continuación

EKA 164, EKA 166 o AKM ajustes

En las páginas siguientes, se muestran las funciones del controla-
dor como se ven en el display EKA 164, EKA 166 y en el software
del sistema tipo AKM.
Para acceder a los parámetros, mantenga pulsado el botón supe-
rior.
EKA-text
AKM text
Reference
r01
Neutral zone K
r04
Po sensor adjust
r12
Main switch
r13
Night offset K
r23
Po setpoint °C
r24
Comp. ctrl. Ref. °C
r25
Max reference °C
r26
Min Reference °C
r27
Night setback
r28
Pc setpoint °C
r29
Cond. ctrl. Ref. °C
r30
Min Reference °C
r31
Max Reference °C
r32
Pc sensor adjust
r33
Pc Reference mode
r35
Dimensioning tm K
r56
Min tm K
r57
Po °C
Capacity control
c08
Step mode
c10
+ Zone band K
c11
+ Zone delay s
c12
++ Zone delay s
c13
- Zone band K
c14
- Zone delay s
c15
-- Zone delay s
c16
Comp. application
c29
No. of fans
c31
Manual capacity %
c32
Cap. control mode
c33
Po pump down limit°C
AK-PC 710
R/W
Description / Parameter
W
Width of neutral zone for compressor control
W
Calibration of Po sensor
W
"Main switch for start/stop of control
ON: Normal control
OFF: Control is stopped"
W
Displacement value for suction pressure in con¬nection with an active
night setback signal (set in Kelvin)
W
Setting of required reference pressure in °C
R
Actual reference temp. for compressor capacity (incl. external reference
signal, if any)
W
Max. permissible suction pressure reference
W
Min. permissible suction pressure reference
R
Actual status of night setback
W
Setting of desired condensing pressure in °C
R
Reference for condenser in °C
W
Min. permitted condenser pressure reference
W
Max. permitted condenser pressure reference
W
Calibration of Pc sensor
W
"Choice of condenser pressure reference
0: Reference = Pc setpoint
1: The reference is changed as a function of Sc3 the external temperature
signal"
W
Dimensioning mean temperature differential between Sc3 air and Pc
condensing temperature at maximum load (compressor capacity = 100%).
Dimensioning temp difference at max load, typically 8-15 K).
W
Minimum mean temperature difference between Sc3 air and Pc condens-
ing temperature at no load (Compressor capacity = 0%)
R
Suction pressure in °C. (Measured with the Po pressure transmitter)
W
"Select coupling pattern for compressors
0: Sequential: Compressors are cut in/out in strict ac¬cordance with com-
pressor number (FILO)
2: Cyclic: Runtime equalisation between compressors (FIFO)
3: Best fit: Compressors are cut in/out in order to make the best possible fit
to actual load"
W
Width of "+ Zone" above neutral zone
W
Integrationtime in "+ Zone"
W
Integrationtime in "++ Zone"
W
Width of "- Zone" below neutral zone
W
Integrationtime in "- Zone"
W
Integrationtime in "-- Zone"
R
Readout compressor combinations
R
Read out number of fans
W
"Manual setting of compressor capacity
The value is in % of total capacity controlled by the controller"
W
Select whether capacity control is stopped, in manual control or controlled
via PI controller
W
Set the actual pump down limit for the last compressor
Control de capacidad RS8FT405 © Danfoss 03-2013
Range
Default
0,1 – 20,0 K
6,0 K
-10,0 - 10,0 Bar
0,0 bar
"ON: Normal control
OFF
OFF: Control is
stopped"
-25,0 - 25,0 K
0,0 K
-80,0 °C - 30,0 °C
-15,0 °C
-50,0 °C - 80,0 °C
80,0 °C
-80,0 °C - 25,0 °C
-80,0 °C
ON/OFF
-25,0 °C - 90,0 °C
35,0 °C
-25,0 °C - 100,0 °C
10,0 °C
-25,0 °C - 100,0 °C
50,0 °C
-10,0 - 10,0 Bar
0,0 bar
"0: Pc setpoint
1: Floating
1: Floating"
0,0 - 25,0 K
15,0 K
0,0 - 20,0 K
6,0 K
"0: Sequential
2: Cyclic
2: Cyclic
3: Best fit
"
0,1 – 20,0 K
4,0 K
10,0 – 900,0 s
300 s
10,0 – 900,0 s
300 s
0,1 – 20,0 K
3,0 K
10,0 – 900,0 s
150 s
1,0 – 300,0 s
30 s
0: Single step only
0: Single step
4: 1 x variable speed
only
+ single step
0 - 6
0
0 - 100%
0%
0: Manual control
2: Auto
1: OFF
2: Auto
-80,0 °C - 30,0 °C
-40,0 °C
67