P40
Auto ack alarms
Service
u01
Pc °C
u03
Saux 1 °C
u10
Lowliquid level alarm
u21
Suction superheat K
u37
Common fan safety
u44
Sc3 Air on °C
u48
Condenser status
u49
Cond. Cap %
u50
Request Cond. Cap %
u51
Suction status
u52
Compressor Cap %
u53
Request Comp. Cap %
u54
Sd discharge gas °C
u55
Ss suction gas °C
u87
Load shed input 1
u88
HP common safety
u89
LP common safety
U12
Actual setup
U13
Injection ON
70
W
Select whether the controller should auto acknowledge alarms. In stand
alone applications it should be set to Enabled
R
Condensing pressure in °C. (measured with the Pc pressure transmitter)
R
Air temp Saux temperature in °C
R
Actual status of low liquid alarm
R
Superheat in suction line
R
Actual status of common fan safety input
R
Outdoor temperature in °C measured with Sc3 temperature sensor
R
Actual control status of condenser
0=Power up
1=Stopped
2=Manual
3=Alarm
4=Restart
5=Standby
10=Full loaded
11=Running
R
Cut-in condenser capacity in % (of total capacity)
R
Reference for condenser capacity
R
Actual control status of suction group
0=Power up
1=Stopped
2=Manual
3=Alarm
4=Restart
5=Standby
10=Full loaded
11=Running
R
Cut-in compressor capacity in % (of total capacity)
R
Reference for compressor capacity (deviations may be due to time delays)
R
Discharge gas temperature in °C
R
Suction gas temperature in °C
R
Actual status on Load shed input
R
Actual status of common HP safety input for all compressors
R
Actual status of common LP safety input for all compressors
R
Actual selected quic setup
R
Status of the "Injection ON" function
Control de capacidad RS8FT405 © Danfoss 03-2013
0: Enabled
1: Disabled
1: Disabled
ON/OFF
ON/OFF
0-100%
0-100%
0-100%
0-100%
ON/OFF
ON/OFF
ON/OFF
See documenation
for quick selections
ON/OFF
AK-PC 710