Technical data - Switching power supplies CP-S 24/5.0, CP-S 24/10.0, CP-S 24/20.0
o
Data at T
= 25
C, U
= 230 V AC and nominal values, if nothing else indicated
a
e
Type
Technical data
Input (L, N)
Rated input voltage
Input voltage range
Frequency
Current consumption
Power consumption
Inrush current / l
2
t (cold start)
Power failure buffering at nom. load (typ.)
Starting time after applying supply voltage
Transient overvoltage protection
Internal input fuse (apparatus protection), not accessible
Discharge current for PE
Output (L+, L+, L-, L-)
Rated output voltage V
out
Tolerance of the output voltage
Adjustment range of the output voltage
Rated output power
Rated output current I
out
Peak output current (power reserve)
o
Derating T
>60
C (up to max. 70
a
Deviation with
statical load change of 10 - 90 %
dynamical load change of 10 - 90 %
control time
change of the input voltage of + 10 %
Response time U
(10 % - 90 %)
out
Residual ripple and switching peaks (20 MHz)
Parallel connection
Series connection to increase voltage
Resistance to reverse feed
Power factor correction (PFC)
Indication of operational states
Overload performance
Short circuit
Current limitation at short circuit
Starting of capacitive loads
General data
Max. power dissipation
Efficiency
MTBF
Dimensions W x H x D
Electrical connection - input side
Wire size
stranded wire with wire end ferrule
stranded wire without wire end ferrule
solid
stripping length
torque
85 - 264 V AC, 100 - 350 V DC
approx. 1.17 A at Ue = 230 V AC
< 23 A / approx. ? A
typ. < 7.25 A at T
o
C)
56,25 mm x 126 mm x 130 mm
pluggable connecting terminals, actuate only when the power is off
CP-S 24/5.0
110 - 240 V AC/DC
1)
typ. 135 W
2
s
> 100 ms
typ. < 100 ms
4 AT
short-circuit, no-load and overload proof
120 W
5 A
=40
o
C
approx. 11.5 A at T
a
from +60
max. < + 0.3 %
max. < + 4 %
max. < 1 ms
max. < + 0.2 %
typ. < ? ms
< 50 mV
PP
yes, to enable redundancy and to increase capacity, current not symmetrical
yes, for decoupling refer to the data sheet
yes, limited to approx. 35 V DC
green LED ("OUTPUT POWER OK")
continuation with current limitation
approx. 11 A
typ. < 15 W
90 mm x 126 mm x 130 mm
0.2 - 2.5 mm
2
/ 22 - 14 AWG
2
0.2 - 2.5 mm
/ 22 - 14 AWG
0.2 - 2.5 mm
2
/ 22 - 14 AWG
7 mm / 0.27 inches
0,4 Nm
CP-S 24/10.0
Switch setting 110: 110-120 V AC
Switch setting 230: 220-240 V AC
Switch setting 110: 85-132 V AC
Switch setting 230: 184-264 V AC, 220 - 350 V DC
47 - 63 Hz
-
typ. 269 W
-
-
-
Varistors
6.3 AT
< 3.5 mA
24 V DC
- 1 ... + 5 %
fixed
240 W
10 A
=40
o
C
a
o
C 2.5 % per Kelvin
no
approx. 19 A
unlimited
typ. < 29 W
> 88 % at U
= 230 V AC
e
350.000 h
CP-S 24/20.0
-
typ. 538 W
-
-
-
12 AF
480 W
20 A
approx. 21 A at T
=40
o
C
a
approx. 25 A
typ. < 58 W
180 mm x 126 mm x 130 mm
2.5 - 10 mm
2
/ 14 - 8 AWG
2
0.5 - 10 mm
/ 20 - 8 AWG
0.5 - 16 mm
2
/ 20 - 6 AWG
12 mm / 0.47 inches
1.2 - 1.5 Nm