R5.5 to 37 kW VARIABLE SPEED MODBUS TABLE

Register
Variable
(40XXX)
1
Status/Control
3
Package Discharge Pressure
10
After-cooler Discharge Pressure
12
Airend Temperature
19
Separator Pressure Drop
20
Percent Capacity
25
Motor Speed
26
Motor Current
28
DC Link Voltage
30
Motor Voltage
31
Package kW
32
kW Hours
65
Total Hours MSB
66
Total Hours LSB
98
Compressor Type
99
Service Level
100
Service Time Period
103
Dryer Installed
112
Target Pressure
113
Auto Stop Pressure
114
Immediate Stop Pressure
117
Compare Savings To
121
Communication Control ON/OFF
122
Remote Start/Stop ON/OFF
123
Power Out Restart Option (PORO) ON/OFF
124
PORO Time (seconds)
127
Scheduled Start - Day
128
Scheduled Stop - Day
129
Scheduled Start (Hour)
130
Scheduled Start (Minute)
131
Scheduled Stop (Hour)
132
Scheduled Stop (Minute)
133
Rated Pressure
251
VSD Software Version Number
255
Warning Code
256
Alarm Code History
400
Reset Web Logins
80448483 Rev.B
RELEASED 16/Dec/2014 10:49:53 GMT
Table 12 : R5��5 To 37 kW Variable Speed MoDBUS Table
Read/Write
R/W
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/W
R/W
R/W
R/W
R
R
R
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
R
R
R
R/W
Range
0 – 999
Add to (mW hours * 1000)
0 - 2
0=Level 0, 1=Level 1, 2=Level 2
1000 - 8000
65 - 145
(T+1)-(T+10)
ASP–(ASP+10)
ASP = auto stop pressure
0 - 2
0=Geo, 1=Mod, 2=ON/OFF
10 - 600
0 - 9
0 - 9
0 – 23
0 – 59
0 – 23
0 – 59
Writing a 1 value will reset the web logins to
0-1
factory defaults. After the reset is performed
this value shall be set back to 0
EN
Notes
See table 13
See table 14
Increments of 1000
0 = no dryer
T = target pressure
0=OFF
0=OFF
0=OFF
See table 14
See table 14
Divide by 100
See table 15
See table 15
EN-31