3.
2
Connecting the motor output in the
main circuit
The motor output is connected using a 3-pole plug
connector (included in the scope of delivery).
4. Connecting the control wires
U
R
L
S
MAN RES AUT
E
X5
97 96 95
X4
X3
22
1
Click
U
0
R
MAN
Res
AUT
95
96
97
The 24V DC control supply voltage and control voltage
inputs must be operated with power supply modules
according to DIN 19240 (max. 5% residual ripple)!
In order to avoid inductive or capacitive coupling of
noise emissions where long control wires are used, we
recommend the use of shielded wires.
If you want to clamp two conductors under one
terminal point, you must use conductors with the
same conductor cross section!
5. Functions
Block diagramm
MAN
Reset
RES
Auto -
AUT
reset
U
s
T
T
E
R
L
EPLAN-symbol
1/L1 3/L3 5/L3
x2
x1
2/T1 4/T2 6/T3
Visualisation – Status-LEDs
The hybrid motor starter visualises the operating sta-
tuses with a total of four LEDs. The functions of the
LEDs follow the NE 44 NAMUR recommendation.
• A green LED (PWR) indicates the general device
status.
• Left or right rotation of the drive (reverse or forward
running) is indicated by a yellow LED (L or R respec-
tively).
L
• An internal or external error (process error: overcur-
0E
rent, asymmetry, phase failure) is indicated by a red
LED (ERR).
Logic
Reset 2
µP
24
V DC
& Error
24 V DC
97
96
95
95
96 97
Us GND R
L
MAN RES AUT
GND_E
x5
x4
Set /
R L Err PWR
Reset
MOTUS®ContactronControl
L1 L2 L3
Reset
2/T1
6/T3
4/T2
x3
9 A
max.