Olimpia splendid NEXYA S3 Manual De Usuario página 59

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

■ Connect sketch of the indoor unit to outdoor unit: Models 18-24
Air Condition Link-Circuit
INDOOR UNIT
L N
Power supply:
1-Phase 220-240V~
Use 3-core cable 3x1.0mm
INDOOR UNIT
S1 S2
Power supply:
1-Phase 220-240V~
Use 3-core cable 3x1.0mm
²
Optional (unit with twins)
2-core shielded cable
(2 x 0.5mm² )
Power supply: 3-Phase 380-415V~
Mod. 10500 W, 14000 W, 17600 W:
5-core cable 5x2.5mm²
3-Phase Power Supply Outdoor units
INDOOR UNIT
L N
L N
Power supply:
1-Phase 220-240V~
2
Use 3-core cable 3x1.0mm
1-Phase Power Supply Outdoor units
202044790 380
INDOOR UNIT
S1 S2
Power supply:
1-Phase 220-240V~
Use 3-core cable 3x1.0mm ²
²
Optional (unit with twins)
2-core shielded cable
(2 x 0.5mm² )
Power supply:1-Phase 220-240V~
Mod. 5300W - 7100 W: 3-core cable 3x2.5mm²
Mod. 10500 W, 14000 W, 17600 W:
3-core cable 3x4.0mm²
L N
59