Preparation for installing the unit
5. Preparation for installing the unit
When deciding the location of the unit and planning your installation, you must follow a set of guidelines based on
the specifications of the unit. These guidelines are summarized in this chapter.
5.1. Environment
•
These units can be installed indoors and outdoors.
•
Situate the units in a place that is accessible for installation and maintenance work and which allows
access to the control panel.
•
Avoid corrosive environments that may affect the proper operation of the unit.
•
Do not leave objects on top of the unit or its sides, as they may block the ventilation and cause high
temperatures.
•
Do not expose it to direct sunlight.
•
Do not install the units in inhabited rooms, due to the noise produced during operation.
•
If they are installed inside a closed space (room, hut, etc.), provide adequate ventilation. The operating
range of the units depends on the environmental temperature, therefore a lack of ventilation may limit
their capacity.
•
If more than one unit is installed, make sure the hot air extraction of one does not interfere with the
correct ventilation of another, leaving a lateral separation of at least 2 meters.
•
Keep the following minimum distances free of obstacles.