I.6
RESIDUAL RISKS AND HAZARDS THAT
CANNOT BE ELIMINATED
IMPORTANT!
Pay the utmost attention to the signs and symbols
located on the appliance.
Indelible safety instructions have been affixed identifying the potentially
dangerous parts if risks are still posed by the unit, which cannot be
technically eliminated, despite all the precautions taken during the
design phase. The warning labels must not be removed for any reason
whatsoever. A new label must be duly requested from the Spare Parts
Service if it should no longer be legible after having used, for example,
aggressive detergents.
Indicates the presence of live components.
Indicates the presence of moving parts
(belts, fans).
Indicates the presence of hot surfaces
(refrigeration circuit, compressor heads).
Indicates the presence of sharp edges on finned
coils.
I.7
PED CATEGORIES OF PRESSURE
COMPONENTS
List of PED critical components (Directive 2014/68/UE).
Component
Compressor
Safety valve
High pressure switch
Low pressure switch
Liquid receiver
Liquid separator
Finned coil
Evaporator
Oil separator
PED category
I (233÷260) II (265÷2160)
IV
IV
-
II
II
Art. 3 Para. 3
I (233÷250) II (260÷2160)
-
SECTION II: INSTALLATION AND MAINTENANCE
I.8
DESCRIPTION OF COMMANDS AND
CONTROLS
The commands consist of the user interface panel (ref. 1), the general
circuit breaker (ref. 2).
I.8.1

Main disconnection switch

DANGER!
The instructions provided in the unit's wiring
diagrams must be strictly complied with if any
accessories not supplied are connected.
Manually controlled b-type power isolating device (ref. EN 60204-1 §
5.3.2). This switch disconnects the appliance from the mains electrical
power supply.
I.8.2

High and low pressure switches.

DANGER!
The pressure switch is a safety device which
complies with standards in force. If tampered with
and/or modified, it could determine personal
danger.
The unit is equipped with two pressure switches for each individual
circuit. This device monitors two distinct functions:
High pressure switch: it trips to prevent working pressure from rising
excessively in the refrigeration circuit.
Low pressure switch: it monitors so that the low pressure side does
not drop below a certain value.
I.8.3
High and low pressure gauges (GM
accessory)
High pressure gauge: indicates the high pressure value.
Low pressure gauge: indicates the low pressure value.
8