Certification - Federal Signal Global G-SND Manual De Instalación Y Mantenimiento

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Installation and Maintenance Instructions
Keep the unit tightly closed when in operation.
After testing is complete, provide a copy of this instruction sheet
to all personnel.
Brass inserts have the potential to store charge when they are not
plugged. Consideration should be taken to prevent these from
becoming a sparking hazard.
Establish a procedure to routinely check the sounder system for
proper activation and operation.
Failure to follow all safety precautions and instructions may result in
property damage, serious injury, or death.

Certification

Certificate Nos.: ATEX Cert No.: Baseefa15ATEX0155X
Protection:
Standards:
Specific Conditions of Use:
1.
The Modular Audible Device enclosure incorporates a sinter and
the volume is greater than 100 cm
Audible Device in carbon disulphide gas atmospheres is not
permitted.
2.
The Modular Audible Device has external non-metallic surfaces
which may provide electrostatic charging hazard. See the
manufacturer's instructions for further information.
3.
The Modular Audible Device has metallic components in the non-
metallic walls of the enclosure which can store electrical charge
and therefore may provide a potential electrostatic discharge.
6
IECEx Cert No.: IECEx BAS 15.0104X
ATEX coding:
Ex db IIB T5 Gb or Ex db e IIB T5 Gb
Ex tb IIIC T100°C Db IP66
Ex db IIC T4 Gb or Ex db e IIC T4 Gb
Ex tb IIIC T135°C Db IP66
EN60079-0: 2012 +A11:2013, EN60079-1: 2014,
EN60079-7: 2007, EN60079-31: 2014, IEC60079-0: 6
IEC 60079-1:7
Ed., IEC 60079-7: 4
th
IEC 60079-31:2
nd
Model G-SND Global Series Sounder
II 2 G D
(Tamb = -50°C to + 49°C)
(Tamb = -50°C to + 60°C)
Ed.
, therefore use of the Modular
3
Ed.,
th
Ed.,
th

Publicidad

Tabla de contenido
loading

Tabla de contenido