Descargar Imprimir esta página

Nilox 17NXBAON12001 Manual Del Usuario página 31

Publicidad

Idiomas disponibles

Idiomas disponibles

Programmable outlets
The 17NXGCON12001 model is equipped with 2 programmable outlet blocks that can be used to power less critical
loads. In fact, these outlets can be disabled to cut off power to less critical loads when in backup mode or in
overload conditions, to increase more important load autonomy. Start/restart (from Backup->Online) can be
programmed with delays.
Click "Programmable outlet setting" to open the following settings screen.
 Outlet Turn ON After UPS ON: Delayed controlled outlet start after UPS start. Select the delay interval before
the outlet is turned on after the UPS is turned on. Select "0" to turn on the controlled outlet without any delay
from when the UPS is turned on.
 Outlet Turn OFF After AC Failure: Turn off the controlled outlet after mains failure. Select this option to
automatically turn off the outlet (within the specified time range) in the event of UPS input voltage interruption,
to stop less critical loads and permit longer autonomy to more critical loads.
 Outlet Turn ON After AC Recovery: Turn on the controlled outlet after power recovery. Select this option to
automatically turn on the outlet (within the specified time range) when mains voltage is restored (from Backup-
>Mains).
 Outlet Turn OFF when Battery LOW: Turn off the controlled outlet when the battery drops under a certain
level. Select this option to automatically turn off the controlled outlet as soon as residual battery block capacity
drops under a certain level to stop less critical loads and provide longer autonomy to more critical loads.
 Outlet Turn OFF when UPS Overload: Outlet turns off in the event of overload.
automatically turn off the outlets in overload conditions (bypass mode) to allow critical loads to be powered via
bypass without having to turn off the device. Click Setting to set the new settings.
 Manual Control Switch: Manual control switch. Click "On" or "Off" to manually turn programmable outlets on
or off, cancelling all the previous settings.
Select this option to

Publicidad

loading

Este manual también es adecuado para:

17nxbaon11001