Descargar Imprimir esta página

Nilox 17NXBAON12001 Manual Del Usuario página 56

Publicidad

Idiomas disponibles

Idiomas disponibles

Appendix [Technical Features]:
Model
EAN
Name
Power Rating(W) Vin=210-265
Power Rating (VA)
Input
Voltage
Frequency
Output
Voltage
Frequency
Harmonic
Distortion
Waveform
Crest Factor
Transfer
AC->DC
Time
Inverter -> Bypass
Overload
Line Mode
(Vin=210-265)
Battery
Bypass
Battery
Voltage
Quantity
Type
Backup Time min
(50%, 70%, 100%)
Charge Current
Charging Time
Efficiency
Line Mode
ECO Mode
Battery Mode
LCD Display
Diagnostics
Protection
Function
ALARM
Input Connections
17NXGCON38001
8059616333608
UPS Online Pro 1000
900
1000
<7% @ 100% NON Linear Load
0 ms (True Online Topology)
106% - 120% for 30s then bypass
121% - 150% for 10s then bypass
106% - 120% for 30s then shuts down
121% - 150% for 10s then shuts down
>150% immediately shuts down
106% - 120% for 250s then shuts down
121% - 130% for 125s then shuts down
131% - 135% for 50s then shuts down
136% - 145% for 20s then shuts down
146% - 188% for seconds then shuts down
>188% immediately shuts down
24VDC
2
12V@7Ah , Sealed Maintenance Free Lead Acid VRLA Type
6, 3, 1
1,5A
Up to 90%
Up to 96%
Up to 85%
4 LED [Utility Normal, Backup, Fault, Battery Fault]
LCD [ECO, Normal, Battery, Overload, Alarm, Service, Bypass,
Programmable Outlet 1/2, Self-Test, Load/Battery/Vin/Vout/Fin/Fout
Power ON, Front Panel (Select), SW, 24hrs (routine check)
In Normal Mode/Battery Short Circuit (LOAD) Electronic Circuit or output
In bypass Mode input Circuit breaker
Spike Suppression meets EN61000-4-5
Battery Over-drain Two stages: Controlled Battery Low Warning & Cut
Over temperature [Normal mode -> Bypass, Battery mode -> UPS shuts
Overload AC Buzzer continuously alarms
Normal / ECO / CF60Hz / CF50Hz, Cold Start
Battery Mode, Low Battery, Overload, Fault
1xIEC (10A, IEC 320-C14)
17NXGCON11001
8059616333615
UPS Online Pro 2000
1800
2000
170-276V
50Hz±5%
200/208/220/230/240±1%
±1Hz or ±3Hz (Selectable)
<3% @ 100% Linear Load
Pure SineWave
3:1
4 ms
<105%
>150% immediately bypass
Buzzer
<105%
Buzzer
<105%
Buzzer
48VDC
4
6, 3, 1
1A
4 hours to (90%)
Up to 91%
Up to 96%
Up to 85%
level, Error, Status]
Circuit breaker
Off
Battery Overcharge
down]
17NXGCON12001
8059616333622
UPS Online Pro 3000
2700
3000
72VDC
6
6, 3, 1
1A
Up to 92%
Up to 96%
Up to 86%
1xIEC(16A, IEC 320-C20)

Publicidad

loading

Este manual también es adecuado para:

17nxbaon11001