Start/Stop; Settings; Autotest - Ingeteam INGECON SUN 1Play TL M Serie Manual De Instalacion Y Uso

Ocultar thumbs Ver también para INGECON SUN 1Play TL M Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 91
Display control
Reasons for shutdown
Log file that indicates the alarms that have triggered the inverter shutdown, indicating the date and time of the
shutdown.
Reset stop reasons
This option resets the Stop reasons log file.

12.6.3. Start/Stop

The operation of the inverter can be stopped and started manually using this option.

12.6.4. Settings

In this menu you can make the following settings:
Date and time
To modify the date and time of the inverter.
Languages
Selection of the language for the text on the inverter display.
Modbus ID
Assignation of a number that identifies the inverter. In photovoltaic installations with
more than one inverter, each one must be assigned a different number. Ingeteam
recommends using correlative numbering.
Partial deletion
Deletes the partial meters.
Grounding
Not applicable.
Contrast
To adjust the screen contrast of the inverter.
String settings
Not applicable.
Power settings
Reduce the unit power.
Test fans
By accessing this option it is possible to run a test to check the inverter fans are working
properly.
Diesel grid
Intended for hybrid installations whereby the grid is generated by a diesel generator.
From this menu you can select whether or not the inverted is managed using the
INGECON EMS Manager.
Factory reset
This returns the inverter to factory default status.
Auxiliary relay closure
Selection of the reason the auxiliary relay closes. The selectable reasons are: insulation
fault, Vac and Fac out of range values, connected to grid or external load.

Autotest

This menu is only available when the standard selected is CEI 0-21 SPI INTERNAL.
The autotest enables an automatic verification of the grid voltage and frequency limits,
bringing these limits toward the real value of the measurement and ensuring that the
unit disconnects in the set time when the measurement does not comply with the limit.
Local command
This menu is only available when the standard selected is CEI 0-21 SPI INTERNAL.
From this menu you can change the bottom and top frequency limits. These limits must
correspond to the selected standard.
12.6.5. Autotest
Autotest allows for the grid voltage and frequency limits to be tested automatically, checking that the unit
disconnects correctly within the time set by standard. This menu is only available for some standards, such as CEI
0-21 SPI INTERNAL.
During autotest, the disconnection time of the following protections is tested:
Fmax (81>.S1)
Lowest upper limit of the frequency protection.
Fmin (81<.S1)
Highest lower limit of the frequency protection.
Fmax (81>.S2)
Highest upper limit of the frequency protection.
ABE2011IQM01_B - Installation and Operation Manual
Ingeteam
DE
EN
ES
FR
IT
PT
81

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido