2) Applicable standard of water quality for the unit
Table 8-9
PH value
Total hardness
Conductivity
Sulfide ion
Chloride ion
Ammonia ion
8.6.9 Installation of multi-module water system pipeline
Multi-module combination installation involves special design of the unit, so relevant explanation is given as follows.
1) Installation mode of multi-module combination water system pipeline
No.n module
No. (n-1)address
Pump
Fig.8-24 Installation of multi-module (no more than 16 modules)
2) Table of diameter parameters of main inlet and outlet pipes
Table 8-10
Cooling capacity
4
30<4
90<4
130<4
210<4
325<4
510<4
740<4
1300<4
Please pay attention to the following items when installing multiple modules:
- Each module corresponds to an address code which cannot be repeated.
- Main water outlet temperature sensing bulb, target flow controller and auxiliary electric heater are under control of
the main module.
- As the total water outlet temperature sensor (Tw), you must use total oulet temp. sensor (Tw) of the master unit
(sensor length is 10m) see the electrical diagram to locate it. The sensor must be located inside the sheath provided
for that purpose.
- One wired controller must be connected on the main module (master).
- The unit can be started up through the wired controller only after all addresses are set and the aforementioned
LWHPV DUH GHWHUPLQHG 7KH ZLUHG FRQWUROOHU LV P DZD\ IURP WKH RXWGRRU XQLW
6.8~8.0
<70ppm
9FP&
No
<50ppm
No
No.(n-1) module
No.(n-2) address
Total inlet and outlet water pipe inside nominal diameter
CAUTION
86
Sulfate
<50ppm
Silicon
<30ppm
Iron content
<0.3ppm
Sodium ion
No requirement
Calcium ion
<50ppm
/
No.1 module
No.0 address
Drill dead hole at the position,
and move the total effluent
temperature sensor at No.0
address to the position
Tw
DN40
DN50
DN65
DN80
DN100
DN125
DN150
DN200
DN250
/