LOCKED MODE
In this mode neither manual nor automatic operation can
be performed. This mode can be activated by two ways:
– Extracting the padlock slider
– Inserting the auxiliary manual handle, changing to 0
(OFF) position and activating the handle padlockable
lever.
UNIT LOCKING VIA PADLOCKABLE LEVER ACTIVATION
This padlock can be in any position according to
changeover switch I - 0 - II or switch - disconnector 0 - I.
UNIT LOCKING BY AUXILIARY MANUAL HANDLE
This padlock is only allowed at 0 (OFF) position, once
locked, the handle cannot be removed from the MU.
The output signal in between terminals 8 and 9 is only activated when the unit is locked via padlockable lever activation.
ERROR LED
MU has an integrated led for failure indication. It can be activated in any of the below situations:
− Failure due to movement under locked position: The unit shaft has moved with the unit in Locked mode.
− Failure due to final position not reached: The ongoing movement has not been finalized.
− Failure due to broken clutch: A shaft movement has been performed with auxiliary manual handle while the state was AUTO. (see annex 6).
NOTE: Once error led is activated, the MU remains locked.
MU unlocking is only possible by switching OFF and ON power supply.
ANNEXES
Annex 1: changeover switch references
MU range is available for changeover switches in the 160 to 800 Amp range. Power supply
is 230VAC/DC.
Changeover switches I - 0 - II
3 P
A
Code
160
GE0160E
200
GE0200E
200
GE0201E
250
GE0250E
315
GE0315E
400
GE0400E
500
GE0500E
630
GE0630E
800
GE0800E
Annex 2:
DIMENSIONS (mm)
3 P + N
Code
GE0160ET4
GE0200ET4
GE0201ET4
GE0250ET4
GE0315ET4
GE0400ET4
GE0500ET4
GE0630ET4
GE0800ET4
250
76
remove
to lock
remove
to lock
A
160-200
250-400
500-800
103
31
5
68
15
G
B
Motorized unit MU
230VAC/DC
Code
GEX690C
GEX691C
GEX692C
7