6
7 Make function settings according to the system.
Switch
810
No.
Operation
When No. 810 for Dip switch SW4 is set to OFF
When No. 810 for Dip switch SW4 is set to ON
Switch
901
No.
Operation
When No. 901 for Dip switch SW4 is set to OFF
are in the thermo-off state.
When No. 901 for Dip switch SW4 is set to ON
Motor valve is closed while all heat source units (OC/
Switch
917
No.
Operation
When No. 917 for Dip switch SW4 is set to OFF
The relay is closed while the compressor is in operation.
When No. 917 for Dip switch SW4 is set to ON
The relay is closed when cooling or heating operation
signal is received from the controller.
Switch
No.
1
2
3
810
0
1
0
901
1
0
1
917
1
0
1
*Take the following steps for function setting.
1. Set Dip switch SW6-10 to ON.
2. Set Dip switch SW4.
3. Press SWP1 for two seconds or longer to change the settings.
*Use the following setting combination of Dip switches.
No. 901 for Dip switch SW4 is OFF, and No. 917 for Dip switch SW4 is ON.
No. 901 for Dip switch SW4 is ON, and No. 917 for Dip switch SW4 is OFF.
9. Refrigerant piping installation
The pipe is connected via a terminal-branch type connection in which refrigerant
piping from the heat source unit is branched at the terminal and is connected to
each of the indoor units.
branched sections are brazed.
Warning:
Do not use refrigerant other than the type indicated in the manuals
provided with the unit and on the nameplate.
during use, during repair, or at the time of disposal of the unit.
- It may also be in violation of applicable laws.
- MITSUBISHI ELECTRIC CORPORATION cannot be held responsible
for malfunctions or accidents resulting from the use of the wrong type of
refrigerant.
Always use extreme care to prevent the refrigerant gas from leaking while
from any source, such as a gas stove, it breaks down and generates
a poisonous gas which can cause gas poisoning. Never weld in an
unventilated room. Always conduct an inspection for gas leakage after
installation of the refrigerant piping has been completed.
SW4 0: OFF, 1: ON
4
5
6
7
8
9
1
0
1
0
0
1
0
0
0
0
1
1
0
1
0
0
1
1
8
heat source unit.
1. Power on the pump, motor valve, and unit.
controller.
9
allowable range.
Ensure that circulating water temperature is within the allowable range.
Ensure that there is no clogging of the strainer.
When several heat-source units are operated by one pump, ensure that
allowable range regardless of the ON/OFF status of the heat source units
in the system.
[Fig. 8.5.1] (P.4)
A
Heat source unit
C
*
1
Tuning valve
E
*
1
Flow switch
G
Power cable
I
Pump interlock
K
Opening command
*1 These items are not supplied.
*2 Do not connect the power cables to TB9-1 and 2 to supply power to the motor
valve. Doing so may cause damage to the Input/Output board.
10
1
1
1
9.1. Caution
This unit uses refrigerant R410A. Follow the local regulations on materials and
pipe thickness when selecting pipes.
1 Use the following materials for refrigeration piping.
Material: Use copper alloy seamless pipes made of phosphorus
deoxidized copper. Ensure the inside and outside surfaces of
the pipes are clean and free from hazardous sulfur, oxide, dusts,
Size: Refer to item 9.2. for detailed information on refrigerant piping
system.
2 Field-supplied piping often contains dust and other materials. Always blow it
clean with a dry inert gas.
3 Use care to prevent dust, water or other contaminants from entering the
piping during installation.
4 Reduce the number of bending portions as much as possible, and make
bending radii as big as possible.
5 For branching and connecting pipes for indoor and heat source units, use
Indoor twinning pipe kit model
PQRY-P series ONLY
Line branch
Down-stream unit model
Less than 30 in total
CMY-Y102SS-G2
Heat source twinning kit model
PQRY-P series ONLY
Total heat source model
P144 ~ P240
CMY-Q100CBK2
B
*
1
Motor valve
D
*
1
Shutoff valve
F
Water pipe
H
Signal cable
J
Operation ON signal
L
Power supply for motor valve
*
2
Indoor junction pipe kit model
PQRY-P series ONLY
Total indoor model
P72~P96
CMY-R160C-J
Total heat source model
P288 ~ P336
CMY-Q200CBK
27