3.2 Installation(12K,18K)

3.2.1 Location for installing indoor unit
Where there is no obstacle near the air outlet and air can be easily
blown to every corner.
Where drain pipe can extend t outside of the wall from the ceiling
board.
It is preferable to have a special draining facility.
Where the roof is strong enough to bear the weight of indoor unit ,
and in not tend to increasing operation sound and vibration.
Do no put anything near the air inlet grill to obstruct it from air
absorption.
Keep the unit and remote controller 1m or more apart from
television, radio etc.
To prevent the effects of a fluorescent lamps, keep the main
unit from it at least 1.5m.
Avoid installing at a place of greasy dirt or steam.
Over1500mm
3.2.2 Height of ceiling board
Normally, keep it ceiling board 2.5m-3m above the ground.
3.2.3 Indoor unit installation
Pattern board for installation is printed on the packing. Cut off the pattern for opening the false ceiling and
installation suspension bolts.
Measure the distance H between the roof surface and the ceiling board ;
Make four suspending poles with M10 screw thread on both ends (metric system) as the below figure
shown.(processed with 10 pole)
Value of L and L1 are calculated as below:
L1=50mm (when H<255mm,L1=40mm)
L=1.5L1+H-230 (unit: mm)
Turn 4 attached nuts onto the thread ends on the suspending poles as shown below:
Over1500mm
(Note: Below reference is only applicable to a house made of concrete.)
F
L1
Installation and Maintenance
Drain pipe
Ceiling
575 to 590
570(Unit Size)
400
L
13
Roof
Wall
L1