The room setpoint temperature can be set
directly with the room-controlled version.
With the weather-dependent version
(
on screen) the temperature is determined
by a set heating curve. The base and end
points of this curve can be set.
With the REDUCED TEMP temperature level,
the curve can also be adjusted by a
set value.
Base point
outdoor temperature
32
End point
Set heating curve
With weather-dependent control, the base and
end points of the curve can be set. The curve
can be adjusted using the + or – keys for a
temporary change of temperature (see fig. on
page 31).
Setting range
Base point
10–40 ˚C
End point
25–90 ˚C
P adjustment reduction 5–35 K
Frost limit
Set parameters for the heating system
Heating type
Radiator heating Top temperature
Radiator heating Mid temperature
Floor heating
Lowest temperature
Factory settings
+25 ˚C
+60 ˚C
25 K
+3 ˚C
Feed/return temp.
90 / 70
70 / 50
40 / 30