VNT2200A1000
Inline Supply Ventilator
Important Installation Requirements
Failure to comply with these requirements
will result in voided warranty, improper
installation, and service callbacks.
Personal Safety
•
Wear safety glasses while installing the unit.
•
Do not cut into any air conditioning or
electrical line.
•
Follow professional safety standards and
all local codes for plumbing, electrical, and
mechanical considerations.
WARNING
: To reduce the risk of Fire or Electric
Shock, do NOT use this fan with any solid-state
speed control device.
WARNING
: TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR
INJURY TO PERSONS, OBSERVE THE FOLLOWING:
a) Installation work and electrical wiring must be done by qualified
person(s) in accordance with all applicable codes and standards,
including the fire-rated construction.
b) When cutting or drilling into a wall or ceiling, do not damage
electrical wiring and other hidden utilities.
Application Considerations
•
The VNT2200 can be installed in multiple positions,
horizontal or vertical.
•
Install the unit with space to access the main access door
and the side access panel for maintenance and service.
•
To ensure quiet operation, do not install the device directly
on the structural supports of the home.
•
The product is for residential applications only. Must be
installed in accordance with all national and local regulations,
building and safety codes.
Mounting the Inline Supply Ventilator
STEP ONE: Preparation
Ensure you have all parts and tools necessary to perform the
installation. Mounting brackets/hardware are included in the
box.
STEP TWO: Installation Area
The VNT2200 unit should be installed in a mechanical room
or as close to an outside wall as possible.
The contractor should install the unit in an area that allows
the homeowner easy access for maintenance. It is very
important to install an electric receptacle (120 Vac) near the
unit, a separate circuit breaker is also recommended.
Example Installation
FRESH AIR INTAKE DUCT
FRESH AIR
INTAKE HOOD
WITH SCREEN
FRESH
AIR
VENTILATION
CONTROLLER
EXTERIOR
WALL
Tools needed to install Inline Supply
Ventilator
NOTE:
Installation is not recommended in unconditioned
areas such as an attic or crawl space where the
temperature could fall below -40 ºF (-40 ºC) or
exceed 160 ºF (71 ºC).
NOTE:
Minimum distance from exterior is 5 ft. (1.52 m).
NOTE:
Ducting in unconditioned areas must be fully sealed
and insulated, per local ordinances and codes.
NOTE:
The unit must be mounted to something that can
support 30 lbs. (13.6 kg)
STEP THREE: Wiring
Connect control device to the VENT terminals. No tools are
required to install wires to the VENT terminals; Simply push
the wire into the terminal and verify the connection by gently
tugging on the wire. The damper control wires will be pre-
wired in the factory to the AUX terminals (24 V).
STEP FOUR: Checkout
1. Ensure mesh filter (and optional media filter) is installed
and seated correctly.
2. Apply power to the unit by plugging in the 120 V cord.
3. Initiate a ventilation call from each of the external controls.
Verify that the VNT2200 unit turns on.
4. Return the external controls to the desired settings.
5. Inspect the ducting to ensure that there are no kinks and
correct as necessary.
QUICK START GUIDE
POWER
VENTILATOR
FILTER
FURNACE/AIR HANDLER
Standard screwdriver
Level
Duct sealing tape
Hex drivers (5/16 in. studs, 1/4 in. brackets)
AIR FLOW
M36747
33-00248EFS-05