5.3. Motor Overload Protection

Functions relevant for safety are realized by the hybrid motor starter without any external influences.
Special switching techniques are not required.
The wiring of the load current circuit should be implemented as in the above listed examples. In contrast,
the module current supply, however, can be connected directly to the voltage source without a safety re-
lay PSR. This applies for the control.

5.4. Motor with brake

If a motor with brake (connection in the motor terminal board) is connected, the 400 V AC brake must be
connected to the 2/T1 and 6/T3 connections. A 230 V AC brake must be connected to the 4/T2 connection
and the star point of the motor.
Please note the following: The motor current monitoring must be increased by the value of the
brake (nominal current of the brake). Configure the relevant setting on the hybrid motor starter
(refer to point 4.3, page 18)!

5.5. Auxiliary relay connection

Auxiliary relay (e.g. PLC RSC 230UC/21, order no.: 2966207) for activating external brakes or
acknowledgements to the PLC must be connected to the "4T2" and "N" connection of the system.

6. Technical data

Type
Input data
Rated control supply voltage U
Control supply voltage range
Control supply voltage
Rated control supply current
Control input L, R:
Output data
Circuit principle
Rated operating voltage U
Operating voltage range
Load current at 20°C (see 8.2. Derating curve)
Load current at 20°C without safety function and
asymmetry recognition (see 8.2. Derating curve)
Rated operating current I
AC-51
AC-53a
Nominal switching capacity
Order No. ELR W3-24DC/500AC-2I
s
acc. to IEC 60947-1 / UL 508
Switching level "Safe off" < 5 V DC
as per IEC 60947-1 ≤ 40 mA
Switching level "Low" -3...9.6 V DC
Switching level "Safe off" < 0.5 V DC
Switching level "High" 19.2...30 V DC
Input current ≤ 5 mA
Load side ELR...-2I
acc. to IEC 60947-1 500 V AC;
e
acc. to IEC 60947-1
acc. to UL 508
acc. to IEC 60947-1
e
acc. to IEC 60947-4-3
acc. to IEC 60947-4-3
acc. to UL 508
acc. to UL 508
Full Load (power factor = 0.4)
Full Load (power factor = 0.8)
ELR W3-24DC/500AC-9I
ELR W3-230AC/500AC-2I
ELR W3-230AC/500AC-9I
ELR W3-24DC/...
24 V DC
19.2 ... 30 V DC
(32 V DC, max. 1 min.)
Safety output module with bypass,
three-phase disconnection
42 ... 550 V AC
42 ... 500 V AC
0.18...2.4 A
0...2.4 A
2.4 A
2.4 A
2.4 A
0.9 kW (1.2 HP)
1.7 kW (2.2 HP)
2297031
2297057
2297044
2297060
ELR W3-230AC/...
230 V AC (50/60 Hz)
85 ... 253 V AC
< 5 V AC
≤ 4 mA
< 44 V AC
< 5 V AC
85...253 V AC
≤ 7 mA
ELR...-9I
500 V AC;
42 ... 550 V AC
42 ... 500 V AC
0.18(1.2) ... 9.0 A
0 ... 9.0 A
9 A
6.5 A
6.5 A
2.3 kW (3.0 HP)
4.6 kW (6.1 HP)
19