Descargar Imprimir esta página

Emerson EC3-X32 Instrucciones De Funcionamiento página 2

Controlador de recalentamiento con comunicación via tcp/ip

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 16
E C D - 0 0 2 d i s p l a y / k e y p a d u n i t : ( L E D s a n d b u t t o n f u n c t i o n s )
Blinking: valve is opening
ON: valve is fully open
Blinking: valve is closing
ON: valve is fully close
ON: demand
OFF: no demand
Blinking: pump
down
ON: alarm
Prg&Sel (5 sec)
OFF: no alarm
Manual reset for
blinking alarm codes
P r o c e d u r e f o r p a r a me t e r m o d i f i c a t i o n u s i n g E C D - 0 0 2 :
• Note: Some of the functions/parameters (manual control and TCP/IP
configuration) cannot be modified when using ECD-002 comparing to a set-up by
PC via TCP/IP.
Warning:
All alarms are disabled during manual control. We do not recommend
unattended operation of system during manual control.
• The parameters can be accessed via the 4-button keypad. The configuration
parameters are protected by a numerical password. The default password is "12".
To select the parameter configuration:
• Press the PRG button for more than 5 seconds, a flashing "0" is displayed
• Press
or
until "12" is displayed (password)
• Press SEL to confirm password
• Press
or
to show the code of the parameter that must be changed;
• Press SEL to display the selected parameter value;
• Press
or
to increase or decrease the value;
• Press SEL to temporarily confirm the new value and display its code;
• Repeat the procedure from the beginning "press
• To exit and save the new settings: Press PRG to confirm the new values and exit
the parameters modification procedure.
• To exit without modifying any parameters: Do not press any button for at least
60 seconds (TIME OUT).
S p e c i a l F u n c t i o n s :
The Special Functions can be activated by:
• Press
and
together for more than 5 seconds, a flashing "0" is displayed.
• Press
or
until the password is displayed (default = "12").
If password was changed, select the new password.
• Press SEL to confirm password
A "0" is displayed and the Special Function mode is activated.
• Press
or
to select the function. The number of special functions is dynamic
and controller dependent. See list below.
0: Reset controller to factory settings (this action is possible only when digital
input is 0V i.e. open).
1: Displays the current TCP/IP address.
2: Assign temporary 192.168.1.101 as TCP/IP address if EC3-X32 has different
Address.
• Press SEL to activate the function without leaving the special function mode.
• Press PRG to activate the function and leave the special function mode.
Emerson Climate Technologies GmbH
Am Borsigturm 31 I 13507 Berlin I Germany
EC3-X32 Superheat Controller with TCP/IP
communication capability
Parameters setting/saving
Next parameter/
value (higher)
Next parameter/
value (lower)
Selecting/confirming
or
to show..."
www.emersonclimate.eu
Operating instruction
M a i n p a r a me t e r s :
(must be checked and modified if necessary)
Code
Parameter description and choices
H5 Password
u0
System refrigerant
0 = R22
5 = R410A
8 = R407A
12 = R449A
uP Installed pressure sensor type
0 = PT5-07x (for R22 / R134a / R507 / R404A / R407A / R407C /
1 = PT5-18x (for R410A/ R32)
2 = PT5-30x (for R410A / R744 / R32)
3 = PT5-50x (for R744)
ut
Installed valve type
1 = EX4
5 = EX8
9 = FX7
uu
Start valve opening (%)
u9
Start opening duration (second)
uL Low superheat alarm function
0 = disable (for flooded evaporator)
1 = enable auto reset
Cut-out at 0.5K (if it maintains 1 min.); Cut-in immediately at 3K
u5
Superheat set-point (K)
If uL enabled (auto or manual)
If uL disabled
u2
MOP function
0 = disable 1 = enable
u3
MOP set-point (°C) saturation temperature
**) Factory setting is according to selected refrigerant (u0):
+13°C - R22
+7°C - R404A
+50°C - R124
+10°C - R407F
+12°C - R449A
+24°C - R1234ze
*) Min. and Max. setting values are dependent to selected type of
refrigerant
┌┘
5 Units conversion
0 = °C, K, bar
(Psig values are divided by 10. Example: Display 12.5 is 125 psig)
┌┘
1 Value to show
0 = Measured superheat (K) 1 = Measured evaporating pressure, (bar);
2 = Valve opening (%)
4 = Calculated evaporating temperature (°C) from the pressure
u4
Superheat control mode
0 = Standard, 1 = Slow, 2 = intermediate control
uH High superheat alarm function
0 = disable, 1 = enable auto reset
uA High superheat alarm setpoint
ud
High superheat alarm delay, min.
P2 Freeze protection cut-out, °C
P3 Freeze protection cut-in, °C
P4 Freeze protection alarm function
0 = disable, 1 = enable auto-reset,
2 = enable manual reset)
P5 Freeze protection alarm delay, sec.
P6 Pump-down function
(0 = disable, 1 = enable auto-reset)
P7 Pump-down cut-out, barg
P8 Pump-down time delay, sec.
P9 Low pressure alarm function
(0 = disable, 1 = enable auto-reset,
2 = enable manual reset)
PA Low pressure alarm cut-out, barg
Pb Low pressure alarm delay, sec.
Pd Low pressure alarm cut-in, barg
L2 Output logic
0: Alarm = normal, pump down. = normal
1: Alarm = inverse, pump down. = normal
2: Alarm = normal, pump down. = inverse
3: Alarm = inverse, pump down. = inverse
Date: 03.04.2017
Min Max
1
0
1 = R134a
2 = R507 3 = R404A 4 = R407C
6 = R124 7 = R744 (subcritical application)
9 = R407F
10 = R32*
13 = R450A
14 = R513A
0
R407F / R124 / R448A /R449A / R450A / R513A /
R1234ze)
1
2 = EX5
3 = EX6
6 = FX5
7 = FX6
10 = FX7.5
11 = FX8
0
0
0
2 = enable manual reset
3
0.5
0
*
+15°C - R134a
+7°C - R507
+15°C - R407C
+15°C - R410A
-5°C - R744
+10°C - R407A
+10°C - R32
+12°C - R448A
+19°C - R450A
+13°C - R513A
0
1 = °F, R, psig
0
3 = Measured coil-out temperature (°C)
0
16
1
-40
-37
0
5
0
-0,5
0
0
-0,8 17,7
5
-0,5
0
EC3-X32_OI_ML_R13_865008.docx
Factory
Field
setting
setting
199
12
15
1
11 = R448A
15 = R1234ze
3
0
12
5
4 = EX7
8 = FX6.5
12=FX9
100
50
120
5
2
1
30
6
30
6
1
1
*
**
1
0
4
0
2
0
1
40
30
15
3
40
0
43
3
2
0
199
30
1
0
18
0.5
199
30
2
0
0
199
5
18
0.3
3
1

Publicidad

loading