Technical Data; 13 Technical Specifications - Saunier Duval SDH 17-025 NW Manual De Instalación

Ocultar thumbs Ver también para SDH 17-025 NW:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 52

TECHNICAL DATA

13 Technical specifications

Power supply
Cooling Capacity
Power input
Operating current
SEER
Heating Capacity
Power input
Operating current
SCOP
Indoor Unit
Air Flow volume
Sound Pressure level
Outdoor Unit
Air Flow volume
Sound Pressure level
Refrigerant
Refrigerant charge
Compressor type
Expansion system
Pipe Connections
Diameter liquid/gas pipes
Max. piping length*
Max. height IU under OU
Max. height OU under IU
Minimum distance between OU and IU
Chargeless length
Additional charge per metre
Table 13.1 Technical specifications.
WARNING!
a
* Maximum piping length.
The curves made in the refrigerant lines count as one
extra meter per curve.
NOTE:
i
As part of its policy for ongoing improvements of its
products, Saunier Duval reserves the right to modify
these specifications without prior notice.
SDH17-NW-I_EN - 01/15 - Saunier Duval
Units
SDH 17-025 NW
V/Ph/Hz
230/1/50
kW
2,70
kW
0,87
A
3,80
5,60
kW
2,80
kW
0,90
A
4,00
3,80
m 3 /h
300 / 400 / 500 / 600
dB(A)
28 / 34 / 39 / 41
m 3 /h
1800
dB(A)
51
R410A
gr
700
Rotary
EEV
Inches
1/4'' - 3/8''
m
15*
m
10
m
10
m
3
m
5,0
gr
20
SDH 17-035 NW
SDH 17-050 NW
3,50
5,28
1,17
1,63
5,20
7,20
6,10
5,60
4,00
5,80
1,20
1,76
5,30
7,80
4,00
3,80
300 / 400 / 500 / 580
550 / 650 / 780 / 850
30 / 35 / 40 / 42
35 / 40 / 43 / 48
1800
3200
53
56
850
1350
EEV
Capillary
1/4'' - 3/8''
1/4'' - 1/2''
15*
25*
10
10
10
10
3
3
5,0
5,0
20
20
TECHNICAL DATA
SDH 17-065 NW
6,45
2,18
9,70
5,10
7,00
2,22
9,80
3,80
550 / 700 / 800 / 1000
39 / 42 / 47 / 51
4000
58
1800
Capillary
1/4'' - 5/8''
25*
10
10
3
5,0
50
- 21 -
EN
EN

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Sdh 17-035 nwSdh 17-050 nwSdh 17-065 nw

Tabla de contenido