Hitachi RCI Serie Manual De Instalación Y Funcionamiento página 39

Ocultar thumbs Ver también para RCI Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 51
1. Calculating Method of Additional Refrigerant Charge W (kg)
Calculate the additional refrigerant charge amount according to the following method:
Example:
1.1. Additional Refrigerant Charge Calculation for Liquid Piping (W
Calculate the additional refrigerant charge amount for liquid piping as below and see example for model RAS-10HRNM,
and fill in the following table.
Example:
Piper Diameter
Total Pipe
(mm)
Length (m)
12.7
10
9.53
5+5
6.35
10+5
Total Additional Charge Amount for Liquid Pipe (W
1.2. Compensating Rate (P).
O/U MODEL
RAS-8
RAS-10
RAS-12
1.3. Calculation of Total Additional Charge Amount (W kg)
Put weight W1 and precharge refrigerant for piping length (P)
Total Q'ty of Additional Charge W = W1 – P
2. Charging Work
Charge refrigerant (R410A) into the system according to the instructions described in the "Installation Manual".
3. Record of Additional Charge
Record the refrigerant charging quantity in order to facilitate maintenance and servicing activities.
Total refrigerant charge of this system is calculated in the following formula.
Additional
Sub Total
Charge (Kg/m)
Amount (Kg)
0.120
10 x 0.120 = 1.2
0.07
10 x 0.07 = 0.7
0.03
15 x 0.03 = 0.45
) = 2.35 kg
1
P (Kg)
1.6
ATTENTION:
It is not necessary to add or to extract the refrigerant if the
1.6
value of the calculation procedure is smaller than (P).
2.0
Example:
W=
2.35
This System:
W=
Total Additional Charge W
Total Ref. Charge of this System
Date of Ref. Charge Work
Year
Month
Example =
Total Ref. Charge of This System =
This System =
ADDITIONAL REFRIGERANT CHARGE
kg)
1
-
1.6
=
0.75 Kg
-
=
Kg
Day
7.8
+
0.75
=
8.55 Kg
W
+
W
=
0
+
=
Kg
27

Hide quick links:

Publicidad

Tabla de contenido
loading

Tabla de contenido