- COMPLETE LEARNING:
Check if the leaves are closed, and then press the F push-button
for more than 3 seconds: DL10 LED begins flashing and leaf 1
begins the opening movement. The following functions can be
commanded by the OPEN A pulses (by radio control or key push-
button):
1∞ OPEN - Leaf 1 Decelerates at opening (it stops
automatically on reaching the stop limit)
2∞ OPEN - Leaf 2 opening movement begins
3∞ OPEN - Leaf 2 Decelerates at opening (it stops
automatically on reaching the stop limit)
4∞ OPEN - Leaf 2 closing movement begins
5∞ OPEN - Leaf 2 decelerates at closing (it stops
automatically on reaching the stop limit)
6∞ OPEN - Leaf 1 closing movement begins
7∞ OPEN - Leaf 1 Decelerates at closing (it stops
automatically on reaching the stop limit)
The DL10 LED stops flashing and the gate is ready for normal
operation.
Notes:
ïThe deceleration pulse should be supplied a little
earlier with respect to the stop limit to prevent the leaf
reaching it at full speed (it would be taken for an
obstacle).
ïIf only one leaf is present, the entire sequence must
nevertheless be effected. When the leaf has finished
opening, supply 5 Open pulses until the leaf begins to
close, and then resume normal operation.
ïFor a correct operation, the mechanical limit stop
during opening and closing is absolutely necessary.
6.3.4. LEARNING TIMES WITH ENCODER + LIMIT-SWITCHES
Learning with the encoder + Limit-switches can be done in two
different ways:
- SIMPLE LEARNING:
Carry out the same procedure as for limit-switch learning. The
encoder is used only as an obstacle sensor.
- COMPLETE LEARNING:
Carry out the same procedure as for limit-switch learning. The
encoder is used only as an obstacle sensor.
Note:
ïIf some limit-switches are not installed, start the
corresponding deceleration by supplying an Open
pulse (which replaces the limit-switch).
ïIf only one leaf is present, the entire sequence must
nevertheless be effected. When the leaf has finished
opening, supply 5 Open pulses until the leaf begins to
close, and then resume normal operation.
6.4.
PRE-FLASHING
If you wish to increase the equipment's safety level, you can
activate the pre-flashing function which enables the flashing
lamp to go on 5 seconds before the leaf starts to move.
Pre-flashing activation procedure:
1 - check if the gate is closed
2 - open and keep open the Stop contact
3 - check if the DL10 LED is OFF (if lighted, pre-flashing is
already active)
4 - briefly press the F push-button and check if the DL10 LED
lights up.
5 - close the Stop contact (DL10 goes OFF).
Procedure for disabling the function:
1 - check if the gate is closed
2 - open and keep open the Stop contact
3 - check if the DL10 LED is lighted (if OFF, pre-flashing is
already disabled)
4 - briefly press the F push-button and check if the DL10 LED
is OFF.
5 - close the Stop contact
7. OBSTACLE DETECTION
The obstacle detection occurs in the following ways:
ï during the gate opening phase:
If an obstacle is detected during the opening phase of the
gate, the leaves reverse their motion up to the complete gate
re-closure observing the leaf closing delay, if set. At the end of
the closing phase, the gate waits for a new OPEN command
to resume operation.
After having received the OPEN command, the leaves start a
new opening movement. If an obstacle is detected again
(obstacle not removed) the leaf that detects it performs a brief
reversal of motion and then stops, whereas the leaf that does
not detect any obstacle continues the opening movement up
to the opening mechanical stop point. After the mechanical
stop point has been reached, according to the selected
function logic, the control unit starts the pause time count or
waits for an OPEN command.
At the end of the set pause time or when the OPEN command
has been received, the control unit starts a reset phase consisting
in a closing movement of the leaves followed by a gate total
opening in a decelerated way. When the opening stop point
has been reached, the control unit resumes the normal cycle
stored in the memory.
ï during the gate closing phase:
If an obstacle is detected during the closing phase of the gate,
the leaves reverse their motion up to the complete re-opening
of the leaves. At the end of the opening phase, the control unit
behaves according to the selected logic, i.e. it starts the pause
time count if an automatic logic was selected or waits for an
OPEN command.
At the end of the pause time or when the OPEN command has
been received, the leaves start a new closing movement. If the
obstacle persists and is detected again by the gate, the leaf
that detected it stays at rest, whereas the other leaf continues
the closing movement up to the leaf total closure.
When the closing stop point has been reached, the control unit
waits for an OPEN command to resume the operation with a
reset cycle consisting in the opening of the leaves and in the
following re-closure at decelerated speed according to the
selected logic.
8. AUTOMATED SYSTEM TEST
When you have finished programming, check if the system is
operating correctly.
Most important of all, check if the force is adequately adjusted
and if the safety devices are operating correctly.
16