Wiring Example and Selection of Circuit Breaker
MODEL
UAT(Y)(P)180
UAT(Y)(P)240
UAT(Y)(P)280
UAT(Y)(P)320
UAT(Y)(P)450
UAT(Y)(P)500
UAT(Y)(P)700
UAT(Y)(P)850
UAT(Y)(P)C10
UAT(Y)(P)C12
Note:
A main switch or other means for disconnection, having a contact separation in all poles, must be incorporated in fi xed wiring in
accordance with local and national legislation.
•
The unit is to be wired directly from an electrical distribution board either by a circuit breaker (preferred) or HRC fuse.
•
Fix the power supply wiring to control module. Connect control wiring to control terminal block through the control box's hole.
•
Earth wiring must be connected.
•
The power supply cord must be equivalent to H07RN-F which is the minimum requirement, and to be used in protective tube.
• Before working on this unit, isolate from the power supply.
• Electrical wiring to this unit and the remote controller shall be installed in accordance with the appropriate
requirements of the local wiring code.
Ensure the operating temperature is in allowable range.
Cooling (R22)
Cooling Only Unit & Cooling Mode For Heat Pump Unit
54
50
40
30
20
10
0
-5
-10
10
15
Indoor temp. (°C WB)
Heating (R22 & R407C)
Heat Pump Unit Only
20
15
10
5
0
-5
-10
-15
10
15
Indoor temp. (°C DB)
WIRE CONNECTION
POWER CABLE
BREAKER
2
(mm
)
CAPACITY (A)
8.4
8.4
13.3
13.3
13.3
21.2
33.6
42.4
60.0
60.0
! WARNING
OPERATING RANGE
20
24
25
30
20
25
27
30
OVER CURRENT
PROTECTION SWITCH (A)
32
32
50
50
50
63
80
100
125
125
Cooling Only Unit & Cooling Mode For Heat Pump Unit
50
46
40
30
20
10
0
-5
-10
10
Indoor temp. (°C WB)
Note:
•
•
The use of your air conditioner
outside the range of working
temperature and humidity can
result in serious failure.
10
380 ~ 415V, 3N ~ /50
EARTH CABLE
(mm
32
32
50
50
50
63
80
100
125
125
Cooling (R407C)
15
20
24
25
30
WB = Wet Bulb
DB = Dry Bulb
!
CAUTION:
2
over)
8.4
8.4
13.3
13.3
13.3
21.2
33.6
42.4
60.0
60.0