Installation Instructions
MicroLogix 1000 Programmable
Controllers
General Specifications
Description:
Specification: 1761 L
16AWA
Memory Size and
1 K EEPROM (approximately 737 instruction words: 437 data words)
Type
Power Supply
85-264V ac
Voltage
Power
120V ac
12 VA
Supply
Supply
240V ac
18 VA
Usage
Usage
24V dc
Not Applicable
Not
24V dc Sensor
Applicable
Power (V dc at mA)
Max Capacitive
Not
Load (User 24V dc)
Applicable
Power Cycles
50,000 minimum
Operating Temp.
0 C to 55 C (32 F to 131 F) for horizontal mounting
0 C to 45 C (32 F to 113 F) for vertical mounting
Storage Temp.
-40 C to 85 C (-40 F to 185 F)
Operating Humidity
5 to 95% noncondensing
Vibration
Shock
Agency
Certification
Terminal Screw
0.9 N m maximum (8.0 in. lbs)
Torque
Electrostatic
IEC801 2 @ 8K V
Discharge
Radiated
IEC801 3 @ 10 V/m, 27 MHz - 1000 MHz except for
Susceptibility
Fast Transient
IEC801 4 @ 2K V Power Supply, 1K V I/O
Isolation
1500V ac
DIN rail mounted controller is 1g.
Relays are derated an additional 2.5g on 32 pt. controllers.
8
16BWA
32AWA
19 VA
16 VA
26 VA
22 VA
200 mA Not
Applicable
200 µF
Not
Applicable
Operating: 5 Hz to 2k Hz, 0.381 mm (0.015 in.) peak to peak/2.5g panel mounted, 1hr per axis
Non operating: 5 Hz to 2k Hz, 0.762 mm (0.030 in.) peak to peak/5g, 1hr per axis
Operating: 10g peak acceleration (7.5g DIN rail mounted) (11 1 ms duration) 3 times each
direction, each axis
Non operating: 20g peak acceleration (11 1 ms duration), 3 times each direction, each axis
CSA certified
UL listed
CE marked for all applicable directives. (Refer to the MicroLogix
Controllers User Manual [publication number 1761 6.3] for more information regarding
compliance to European Union directives.)
3V/m, 87 MHz - 108 MHz, 174 MHz - 230 MHz, and 470 MHz - 790 MHz
32BWA
32AAA
16BBB
20.4-26.4V dc
Not Applicable
24 VA
16 VA
30 VA
22 VA
5 VA
200 mA
Not Applicable
200 µF
16BWB
32BBB
32BWB
5 VA
7 VA
7 VA
1000 Programmable