S19-270C, S19-270E, S19274C, S19274E
Installation
— Left-Hand Units (Classic)
Classic eyewash unit is shown. Classic eye/face wash unit is similar.
Apply pipe sealant (supplied by installer) to all male-threaded pipe joints.
8
Rotate the bent arm 180°
around the valve . Using
low strength thread locker,
C
reinstall the set screw
into the valve in the new
location shown until it
bottoms out, then back off
½ turn .
Arm must swing freely .
10/5/2017
Remove the sprayhead from the
bent arm . Remove the set screw
A
from the valve assembly with an
Allen key (1/16"(1 .5mm)) . Set
the two items aside .
Mount the unit onto the deck . Refer to the instructions on page 6 for
E
eyewash units or page 7 for eye/face wash units .
The left-hand unit must be installed on the left side of the deck .
Slowly open the water supply lines to
F
relieve air and pressurize the valve . Test
the unit for leaks and adequate flow .
B
Rotate the bent arm
180° around the valve .
D
Reattach the sprayhead to the
bent arm, resealing as necessary .