7
Fitting and commissioning
7.1
CORREX
®
MP 1.9-900 for sleeve mounting
Note: Observe the instructions set out in chapter 2.3 above
7.1.1 Safety instructions for fitting:
1. Remove any existing magnesium protection anode before installing the
CORREX
2. Never connect the plug-in potentiostat to magnesium protection anodes.
3. The titanium anode must not be in direct contact with internal tank
components or with the tank wall. The quality of the insulation must be
checked with a suitable measuring instrument (e.g digital multimeter or
CorroScout
be immersed in water.
4. The function of the CORREX
parts are safely connected by metallic conductors. The quality of the galvanic
connections must be checked with a suitable measuring instrument (e.g digital
multimeter or CorroScout
5. Use only the original connecting cables
6. Never extend the connecting cables: otherwise risk of connection with
wrong polarity and thus of increased corrosion.
7. Check before commissioning that the cables are not interchanged.
Interchanging the cables results in increased corrosion.
8. For optimal results, the sealing ring needs a 60° chamfer at the sleeve.
Note: If the CORREX
any existing threaded sleeves can be used, if necessary with reducers (stain-
less steel or brass, red bronze). Any tampering with system components such
as the connecting cable results in the expiration of the legal warranty.
7.1.2 Drawing: Fitting and commissioning
The illustration on the fold-out page (chapter 1.1) of this manual shows an
example of the installation procedure for a CORREX
screw fitting set. The actual situation depends on tank type, tank size, type of
anode and connecting cable used.
Note: Leave the fold-out page (chapter 1.1) open when installing the system.
The following parts are needed for installation:
1. Titanium anode with screw fitting G 3/4"(chapter 1.2, scope of supply (1))
2. Connecting cable (chapter 1.2, scope of supply (3))
3. Plug-in potentiostat (2)
®
MP 1.9-900 system (in case of retrofitting).
®
500). During this measurement, the titanium anode must not
®
500).
®
MP 1.9-900 system is installed by way of retrofitting,
Operating Instructions CORREX
®
MP 1.9-900 system is only ensured if all electrical
®
MP 1.9-900
®
MP 1.9-900 system with
27