Additional Information For Switchgear Positioning - ABB MNS R Manual De Instalación

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Splice bar
Threaded rivet
4.2.2

Additional Information for Switchgear Positioning

Minimum distance around the compartments, on the front and rear sides, must be at least 1200 mm
(see Figure).
To install the last compartment (right), the distance between the last compartment and the wall (right)
must be 150 mm.
In case of compartments, with doors installed on the left side, the minimum distance between the left
wall and the last left compartment must be 150 mm, so the doors can be opened in an angle of more
than 90°.
The distance between the upper edge of the highest cubicle end and the ceiling must be min. 500 mm
for cubicles which are internal arc proof (see Figure).