To do this push both INCR/DECR buttons for 5 sec, till when on the di-
splay appears CONF. Now you are in the programmation so just click
SET to scroll all parameters.
The parameters for the user are:
SP.Lo: % of minimum speed (generally 10%, so fans does not work under the 10% of the maxi-
mum speed)
SP.Hi: % of maximum speed (it can be 100% or less and it indicates that at full speed, fans go to
the 100% of the maximum speed of the machine)
P.b: is the proportional band, the °C/°F range in which the fan goes from the minimum speed to
the maximum one; for the industrial sector generally is set up on 20°C.
NOTE: in mode A, the proportional band is already set up when the wind speed is chosen (see
SETTINGS); in fact setting for example 8 m/s, blades have the max RPM at 0 m/s and min ones
at 8 m/s.
AnEM: turn on/turn off wind block when the wind speed is the same or upper then the value
set up with the SET button; put 0 to turn AnEM off and 1 to turn it on. In the industrial sector
generally is 0.
Push SET to quit.

OTHER FUNCTIONS AND RESET

With the VORT T other functions are available. In particular:
Reading Record Max/Min: pushing the INCR button
the maximum temperature (Mod B) or wind speed (Mod A) recorded.
Pushind the DECR button
Keeping one of the 2 button pushed for 5 sec, all records are cancelled.
Reading % output: pushing the ACTION button is possible seeing the % of the fans speed in
that moment.
If it is necessary doing a reset with the initial default values of the control box, when the box is turn
on, keep pushed the INCR button till when on the dispaly appears BOOT. Then stop pushing INCR
and wait for the reset of the electronic machine.
is possible reading the minimum record.
is possible reading the record of
9