Descargar Imprimir esta página

RHOSS H58624/B Instrucciones De Uso página 38

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

2.2.2 Fast Hot Water
At the Function setting page with the unit turned off, by touching "Fast hot water", the control panel will go to the corresponding setting page,
where desired option can be selected. Then by pressing "OK" this setting will be saved and the control panel will back to the function setting page.
This function enables the electrical resistance of the water storage. For the operating logic, refer to paragraph 2.5.17 Control Logic of the Water
Tank Heater.
NOTE
This function can be set to "On" only if the water tank is available.
The setting is memorized and re-proposed in case of power failure (see 2.6.1 On/Off memory).
The default value is Off.
2.2.3 Cool + Hot water
At the Function setting page with the unit turned off, by touching "Cool + Hot water", the display panel will go to the corresponding setting page,
where desired option can be selected. Then by pressing "OK" this setting will be saved and the control panel will back to the function setting page.
This function defines the priority:
Cool
=> the system has the priority
Hot water => the Hot water has the priority
NOTE
If the water tank is not enabled, this function is not available.
If the water tank is enabled, the default priority is given to ACS.
The setting is memorized and re-proposed in case of power failure (see 2.6.1 On/Off memory).
The default value is Cool.
2.2.4 Heat + Hot water
At the Function setting page with the unit turned off, by touching "Heat + Hot water", the control panel will go to the corresponding setting page,
where desired option can be selected. Then by pressing "OK" this setting will be saved and the display panel will back to the function setting page.
This function defines the priority:
Heat
=> the system has the priority
Hot water => the Hot water has the priority
NOTE
If the water tank is not enabled, this function is not available.
If the water tank is enabled, the default priority is given to ACS.
The setting is memorized and re-proposed in case of power failure (see 2.6.1 On/Off memory).
The default value is Heat.
38
ELECTA-ECO

Publicidad

loading

Productos relacionados para RHOSS H58624/B