2.5.12 Force Mode
At the commissioning parameter setting page, by touching "Force mode", the control panel will access to the corresponding setting page.
At the "Force mode" setting page, it can be set to "Force-cool", 'Force-heat" and "Off".
When it is set to "Force-cool" or "Force-heat", the control panel will directly go back to the homepage and response to any touching operation
except the ON/OFF operation, with a window popping up, saying "The force-mode is running!". By touching ON/OFF, "Force mode" will quit.
NOTE
This function is allowed only when the unit has just repowered and not turned on. For the unit which once has been put into operation, this
function is unavailable, alerting "Wrong operation!".
This setting will not be memorized upon power failure.
The default value is Off.
2.5.13 Gate-Ctrl (remote ON/OFF)
At the commissioning parameter setting page, by touching "Gate-Ctrl.", the control panel will access to the corresponding setting page.
When "Gate-Ctrl." has been activated, the display panel will detect the contact on 27-28 on terminal board:
If the contact is CLOSE, the unit will run normally.
If the contact is OPEN, the controller will turn off the unit at once and back to the homepage. In this case, all touching operation
become ineffective and a prompt dialog box will pop up.
NOTE
Before activating the function, make sure have connected a device to the terminals that opens or closes the contact. Otherwise the unit
stops.
The setting is memorized and re-proposed in case of power failure (see 2.6.1 On/Off memory).
The default value is Off.
53
ELECTA-ECO