Select "Period 1" or "Period 2" and a window will pop up, where time period can be set.
Then select "WT-Heat1/2" or "WT-Cool 1/2" and also a window will pop up where temperature can be set.
After that, by touching the "Save" icon, all settings will be saved.
NOTE
"Temp. Timer" is a repetitive daily timer
This setting is valid only when the unit is turned on.
Under the "Cool" or "Cool+Hot water" mode, the setting possible is "WT-Cool"; while under the "Heat" or "Heat+Hot water" mode,
the setting targets possible is "WT-Heat".
When start time of period 2 is the same as that of period 1, then the former takes prevalence.
"Temp.timer" is judged based on timer.
During this setting, when temperature is set manually, then this setting will take prevalence.
Under the "Hot water" mode, this function will be reserved.
The priority of the timers is as follows: Time bands (high) - Timer - Preset mode - Weekly timer (low)
The setting is memorized and re-proposed in case of power failure (see 2.6.1 On/Off memory).
The default value is Off.

2.2.12 Emergency Mode

At the Function setting page, by touching "Emergency Mode", it will go access to the "Emergency Mode" setting page. At the setting page, it can be
set the mode to "On" or "Off".
This function, for the production of hot water (sanitary or plant), deactivates the heat pump and activates an additional heat source or an electric
heater.
When "Emergen.mode" has activated, the corresponding icon will appear at the upper side of the menu page. When the mode is not set to
"Heat" or "Hot water", the display panel will tell "Wrong running mode!"
NOTE
The emergency mode is allowed on conditions that there is some error or protection and the compressor has stopped at least for
three minutes.
Under the emergency mode, "Hot water" or "Heat" cannot be performed at the same time.
The unit can enter "Emergency Mode" only if the operating mode is set to "Heating" or "ACS" and "Gen.Cal. Additional" or
"Electrical Resistance" is set to "Active".
When the unit performs "Heat" under "Emergen. mode" and the controller detects "HP-Water Switch", "Auxi. heater 1", "Auxi. heater
1", and "Temp-AHLW" "Auxi.heater 2" errors, this mode will quit at once. In the same way, when errors mentioned above occur,
"Emergen. mode" cannot be activated.
When the unit performs "Hot water" under "Emergen. mode" and the controller detects "HP-Water Switch" error, this mode will quit
at once. In the same way, when errors mentioned above occur, "Emergen. mode" cannot be activated.
When this function has been activated, "Weekly timer", "Preset mode", "Clock timer",and "Temp timer" will be deactivated. Beside
"On/Off", "Mode", "Quiet mode", "Weekly timer", "Preset mode", "Clock timer" and "Temp timer" operation are unavailable.
Under "Emergen. mode", the thermostat does not work.
This function can be activated only when the unit is turned off. If dosing so with the unit keeping "On", a window will pop up, saying
"Please turn off the system first!".
"Floor debug", "Disinfection" and "Holiday mode" cannot be activated at the same with this function. When doing so, a window will
pop up, saying "Please disable the emergen. mode!".
Upon power failure, "Emergen. mode" will back to "Off".
The default value is Off.