Catalog Number • Numéro de Catalogue • Número de Catálogo: CX-100
Country of Origin: Made in China • Pays d'origine: Fabriqué en Chine • País de origen: Hecho en China
CX-100-U is BAA and TAA compliant (Product produced in the U.S.)
The CX-100 is a 24VDC passive infrared (PIR) occupancy sensor which controls lighting and HVAC systems based on occupancy. It
also has a light level feature that can be used to keep sections of lights from turning on if the ambient light level is sufficient. The CX-100
contains an isolated relay with Normally Open and Normally Closed outputs for interfacing with HVAC or EMS.
PIR sensing systems are passive systems which react to changes in infrared energy (moving body heat) within the coverage area. PIR
sensors must directly "see" motion of an occupant to detect them, so careful consideration must be given to sensor placement.
Coverages shown are maximum and represent coverage for walking motion. Actual coverage will vary slightly depending on mounting
height and furnishings.
Masking the lens: Opaque adhesive tape is supplied so that sections of the sensor's lens can be masked. This restricts the sensor's
view and allows you to eliminate coverage in unwanted areas.
Dense Wide Angle Lens (Standard)
up to 2000 sq ft for walking motion
up to 1000 sq ft for desktop motion
Two-Sided Aisleway Lens (-3)
up to 134 linear ft for walking motion
Wattstopper
PIR Occupancy Sensor with Light Level and Isolated Relay
Détecteur de Mouvement IRP avec contrôle du niveau de luminosité
et relais isolé
Sensor de Ocupación PIR con nivel de luz y relé aislado
Installation Instructions • Instructions d'Installation • Instrucciones de Instalación
UNIT DESCRIPTION
COVERAGE PATTERNS
®
SPECIFICATIONS
Voltage ................................................................. 24VDC
Current Consumption ............................................. 19mA*
Power Supply ............................ Wattstopper Power Pack
Isolated Relay Rating .................................... 1A@24VDC
Time Adjustment ........................ 15 seconds—30 minutes
Sensitivity Adjustment ..................... Minimum—Maximum
Light Level Adjustment ..................................... 3—200FC
*Current consumption can be slightly higher when only one
sensor per power pack is used.
Long Range Lens (-1)
up to 90 linear ft for walking motion
One-Sided Aisleway Lens (-4)
up to 50 linear ft for walking motion

Publicidad

Tabla de contenido

Solución de problemas

loading

Resumen de contenidos para LEGRAND Wattstopper CX-100

  • Página 1 Wattstopper ® PIR Occupancy Sensor with Light Level and Isolated Relay Détecteur de Mouvement IRP avec contrôle du niveau de luminosité et relais isolé No: 24227 – 11/16 rev. 1 Sensor de Ocupación PIR con nivel de luz y relé aislado Installation Instructions •...
  • Página 2 INSTALLATION Fig. A The CX-100 sensors can be mounted to walls or ceilings with the supplied swivel bracket, and the supplied junction box cover plate if necessary (see figure C). Mounting at fixture height is most effective. The -3 & -4 sensors can also be mounted to industrial fixtures by using the MB-1 industrial mount bracket.
  • Página 3 WIRING DIRECTIONS Occupancy and Light Level Controlled Lighting WARNING: TURN THE POWER OFF AT THE CIRCUIT BREAKER BEFORE WIRING. Each Wattstopper BZ series power pack can supply power for up to 6 CX-100 sensors. When using more sensors than this, multiple power packs are required.
  • Página 4: Troubleshooting

    1. Set the Time Delay to minimum, 15 seconds. 2. Set the Light Level trimpot to minimum, fully counterclockwise. 3. Be still and allow the lights to turn off. 4. Move a hand in front of sensor every 10 seconds (to keep sensor activated), and without blocking any light from reaching the sensor, in small increments, turn Light Level adjustment toward maximum, waiting at least 5 seconds between increments, until the lights turn on.
  • Página 5: Description De L'appareil

    INSTRUCTIONS EN FRANÇAIS DESCRIPTION DE L'APPAREIL CARACTÉRISTIQUES Le CX-100 est un détecteur de présence infrarouge passif (IRP) 24 Tension ................24 V CC V CC qui contrôle l'éclairage et les systèmes CVCA en fonction de la Consommation actuelle .............19 mA* présence. Il possède également une fonction de niveau d'éclairage Alimentation électrique .....
  • Página 6: Instructions De Câblage

    4. Raccordez le détecteur au support de base en penchant le support de montant de sorte qu'il soit aligné avec l'encoche en demi-cercle, comme illustré dans la figure A. Poussez la boule dans l'ouverture du support de base jusqu'à ce qu'elle se mette à...
  • Página 7 Câblage D'UNE CHARGE D'ÉCLAIRAGE CONTRÔLÉE PAR LA PRÉSENCE ET D'UNE SECONDE CHARGE CONTRÔLÉE PAR LA PRÉSENCE ET LE NIVEAU DE LUMINOSITÉ (ÉCLAIRAGE AMBIANT) – raccordez: • le fil BLEU du bloc d'alimentation au fil JAUNE du capteur. Plusieurs détecteurs et systèmes d'éclairage •...
  • Página 8: Dépannage

    DÉPANNAGE Les lumières ne s'allument pas en cas de présence, et la condition suivante est présente: La DEL ne clignote pas: Lorsque le détecteur est mis sous tension pour la première fois, il passe tout d'abord par une période de réchauffement de 60 secondes maximum avant que la DEL ne soit activée.
  • Página 9: Descripción De La Unidad

    INSTRUCCIONES EN ESPAÑOL DESCRIPCIÓN DE LA UNIDAD ESPECIFICACIONES El CX-100 es un sensor de ocupación infrarrojo pasivo (PIR) de Voltaje ................24 V CC 24 V CC que controla los sistemas de iluminación y de climatización Consumo de corriente ............19 mA* en función de la ocupación.
  • Página 10: Instrucciones De Cableado

    4. Conecte los sensores al soporte de la base inclinando el soporte del puesto de manera que quede alineado con la muesca en forma de semicírculo, como se ilustra en la figura A. Empuje la bola dentro de la apertura del soporte de la base hasta que encastre en su lugar, teniendo cuidado de no pinchar los cables.
  • Página 11: Ajuste Del Sensor

    Cableado DE UNA SOLA CARGA DE ILUMINACIÓN PARA CONTROL DE OCUPACIÓN, Y UNA SEGUNDA CARGA PARA CONTROL DE OCUPACIÓN Y NIVEL DE LUZ (LUZ AMBIENTE-conectar: • Cable AZUL desde la fuente de alimentación al cable AMARILLO del sensor. • Cable AZUL desde la fuente esclavo al cable AZUL del sensor. •...
  • Página 12: Información Para Pedidos

    No. 24227 – 11/16 rev. 1 © Copyright 2016 Legrand All Rights Reserved. 800.879.8585 © Copyright 2016 Tous droits réservés Legrand. www.legrand.us/wattstopper © Copyright 2016 Legrand Todos los derechos reservados.

Este manual también es adecuado para:

Wattstopper cx-100-3

Tabla de contenido