Some equiptment, like relays, gates or
motors, can damage the CX controller by
magnetic induction, when it switches off.
To prevent this, reverse connect the diode
(such as 1N5401 .. 1N5408) between LOAD +
and LOAD - as shown in the left diagram.
Fasten the strain relieves.
If you intend to use the Excess Energy
Management output, follow these steps:
a. Remove the green terminal block in the
terminal compartment.
b. Mount the excess energy signal wires as
shown in the picture beside.
c. Connect the signal wires to the excess
energy management input of the appropriate
load (e.g. Phocos DCL DC voltage converter
and Phocos BCM DC battery charger).
d. Reconnect the green terminal block to the
CX.
29