Installer Setting - Static Pressure Step Setting - Friedrich DWC1 Manual De Instalación Y Operaciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Installer Setting - Static Pressure Step Setting

This function is applied to only duct type. Setting this in other cases will cause malfunction.
This function is only available on some models.
This is the function that static pressure of the product is divided in 11 steps for setting.
• Static Pressure (Code 06) setting will not be used if Static Pressure Step (Code 32)
setting is being used.
• For the static pressure value for each step, refer to the indoor unit in the product
manual.
Press
button for 4 seconds to
1
enter the installer setting mode until
timer segment displays "01:01".
If pressing
button repeatedly, it
2
moves to static pressure selection menu
as picture below.
Select static pressure by pressing
3
button.
00: use static pressure (code 06) set value
01~ 11: static pressure step (code 32) set value
Function Code
pressure
Press
button to save.
4
Pressing
button will exit settings mode.
5
❈ After setup, it automatically gets out of
setup mode if there is no button input for
25 seconds.
❈ When exiting without pressing set button,
the manipulated value is not reflected.
Owner's & Installation Manual 21
Installation instruction

Publicidad

Tabla de contenido
loading

Productos relacionados para Friedrich DWC1

Tabla de contenido