Installation
5 - Using EnviroSense
SRCOOLNET supports the use of the included EnviroSense environmental sensor to
control the SRCOOL12K setpoint instead of the temperature sensor in the return
airstream. This helps ensure that supply air to important equipment is at or below a
target temperature in cases where SRCOOL12K is indirectly supplying cold air to that
equipment.
5-1
Important Considerations When Using Remote Temperature Setpoint Mode
It is important to keep the following considerations in mind when using the Remote
Temperature Setpoint feature of SRCOOLNET:
1
The temperature being used for controlling the status of the attached cooling
device is the EnviroSense sensor, NOT the return air temperature. The return air
temperature may be higher or lower than the temperature Envirosense is
reporting.
2
The setpoint displayed on the attached cooling device display panel will probably
NOT match the Remote Setpoint Temperature specified. Typically the setpoint
temperature displayed on the device display panel will be the minimum (when
cooling) or maximum (when not cooling) setpoint permissible by the cooling unit.
3
If the return air temperature at the air intake of the cooling device is outside the
limits of the cooling device, the Remote Temperature Setpoint mode will be
unable to control the temperature at the Envirosense sensor. For this reason it is
important to ensure that the cooling unit air intake temperature be between 17 °C
and 30 °C for the Remote Temperature Setpoint to work correctly.
4
If the power button on the cooling unit display panel is pressed while in Remote
Temperature Setpoint mode, the mode will be canceled.