Fault
Reason
Does not switch
No power or power too low
(green LED does not light up)
Electronic defective
Contacts welded together
(after short-circuit)
Microwave barrier defective
Switches incorrectly
Incorrect setting of change-
over switch for limit signal
Permanent alarm
Interrupt or short-circuit line
signal
to microwave barrier
Microwave barrier defective
Endress+Hauser
Remedy
Check power
6
È
Replace FTR325
Replace FTR325, connect a
fuse into contactor circuit
Replace microwave barrier and
send it to the manufactor for
reconditioning
Correctly set change-over
switch behind front panel
19
È
Check line and connections
13
È
Replace microwave barrier and
send it to the manufactor for
reconditioning
en - Troubleshooting