Vanderbilt SPCE651 Manual De Instrucciones página 2

Tabla de contenido

Publicidad

English –Instructions
WARNING: This device shall only be connected to power supplies compliant
to EN60950-1, chapter 2.5 ("limited power source").
When changing or installing a SPCE650/651/652 on the SPC-series system,
ensure that all anti-static precautions are adhered to while handling
connectors, wires, terminals and PCBs.
EC Declaration of Conformity
Hereby, Vanderbilt International (IRL) Ltd declares that this equipment type, is in
compliance with all relevant EU Directives for CE marking. From 20/04/2016 it is in
compliance with Directive 2014/30/EU (Electromagnetic Compatibility Directive).
The full text of the EU declaration of conformity is available at:
http://pcd.vanderbiltindustries.com/doc/SPC
Introduction to the SPCE650/651/652
The SPCE650/651/652 allows an existing system to be expanded externally
providing additional zone inputs and relay outputs.
The SPCE650/651/652 incorporates the following elements, as shown in Fig. 1.
1. Front tamper switch: The Expander has a front tamper switch with spring.
When the lid is closed the spring closes the switch.
2. Tamper by-pass [J1]: The jumper setting determines the operation of the
tamper. The tamper operation can be overridden by fitting J1. The engineer
must ensure that J1 is removed before leaving site for the system to comply
with standards.
3. Buzzer: The buzzer is activated in order to locate the expander (see SPC
Configuration Manual).
4. Back tamper by-pass [JP6].
5. Manual addressing switches: The switches allow manual setting of the ID of
each expander in the system.
6. X-BUS Status LED: The LED indicates the status of the X-BUS when the
system is in FULL ENGINEER mode, as shown below:
LED status
Flashes regularly
(once every 1.5 seconds approx.)
Flashes quickly
(once every 0.2 seconds approx.)
7. Outputs: The expander provides 2 programmable outputs for use on the SPC-
series system.
8. Inputs: The expander has 8 on-board zone inputs that can be configured as
intruder alarm zones on the SPC-series system.
9. Auxiliary Power Supply (12 V): These are used to power auxiliary devices to
a maximum of 200 mA.
10. Input Power: The expander requires 12 V DC that can be supplied directly
from the SPC-series controller or from a SPC PSU expander.
11. X-BUS Interface: The communication bus is used to connect expanders
together on the SPC-series system (see section Wiring the X-BUS interface).
12. Termination Jumper: This jumper as a default is always fitted, however,
when wiring for Star configuration this fitting should be removed (see section
Wiring the X-BUS interface).
13. PSU 4-pin Interface: Connects to item 9, Power and Data Connector, with a
straight through cable.
SPCE651
The SPCE651 enables inertia type sensors to be connected to the zone inputs. It
is important that the inertia sensor is calibrated and the correct pulse count and
gross attack settings are programmed correctly. Refer to the Installation and
Configuration manual for details on configuring analyzed expanders.
SPCE652
Please ensure the back tamper spring has been fitted to the underside of the
expander housing. The spring should be perpendicular to the exit aperture hole
and be firmly connected to the switch plunger on the internal PCB.
Wiring the X-BUS interface
The X-BUS interface provides connection of expanders and keypads to the SPC
controller. The X-BUS can be wired in a number of different configurations
depending on the installation requirements.
NOTE: Maximum system cable length = number of expanders and keypads in the
system x maximum distance for cable type.
Cable type
CQR standard alarm cable
UTP category: 5 (solid core)
Belden 9829
IYSTY 2 x 2 x 0.6 (min)
Fig. 2 shows the wiring of the X-BUS to an expander/controller and the following
expander/ controller in Spur configuration. Terminals 3A/3B and 4A/4B are only
used for using a branch wiring technique. If using a Spur configuration, the last
expander is not wired back to the controller.
See Fig. 2: Wiring of expanders
SPC controller
1
Previous expander
2
Description
The X-BUS communications status is OK.
Indicates the last in line expander
(excludes star and multi-drop
configuration)
Distance
200 m
400 m
400 m
400 m
SPCE650/651/652
3
Next expander
4
Please refer to SPC Configuration Manual of connected controller for further wiring
instructions, shielding, specifications and limitations.
Wiring the Inputs
The SPCE650/651/652 has 8 on-board zone inputs that can be configured to be
one of the following:
No End of Line (NEOL)
Single End of Line (SEOL)
Dual End of Line (DEOL) (Figure 3)
Anti-Masking PIR (Figure 4)
See Fig. 3: Default configuration (DEOL 4K7)
COM
1
Input X
2
Tamper
3
Alarm 4K7
4
EOL 4K7
5
See Fig. 4: Anti-Masking PIR configuration
COM
1
Input X
2
Tamper
3
Alarm 1K
4
EOL 2K2
5
EOL 1K
6
Please refer to SPC Configuration Manual for all possible resistor values and
combinations.
Anti-Masking is only reported as "Alarm" type to ARC and if area or
system is set.
Wiring the outputs
The SPCE650/651/652 has 2 on-board 1-A, single pole changeover relays that
can be assigned to any of the SPC system outputs. These relay outputs can switch
a rated voltage of 30 V DC (non-inductive load).
Fig. 5 shows the wiring of an active high output. When the relay is activated, the
common terminal connection (COM) is switched from the Normally Closed terminal
(NC) to the Normally Open terminal (NO).
See Fig. 5: Wiring of a standard +12 V Siren
Normally Open terminal (NO)
1
Common terminal connection (COM)
2
Normally Closed terminal (NC)
3
X-BUS addressing
For further addressing, reconfiguration, device location, monitoring, editing of
names, X-BUS type of communication, failure timer please refer to SPC
Configuration Manual.
Appendix
See Fig. 6: SPCE650/651/652 Enclosure specifications
Expander anchor points
1
Wall spacers
2
Cover anchor points
3
Cable grips
4
Mounting holes
5
Cable entry holes
6
Cable ties
7
Cover hooks
8
See Fig. 7: Expander cover
Front tamper guide
1
Cover fixing screws
2
Mounting Expander in SPC Hinged Enclosure
The SPCE650/651/652 may also be installed in a hinged enclosure. This
enclosure can accommodate:
1 battery (17 Ah max.), 1 SPC controller and a 4 I/O expanders (optional)
1 battery (17 Ah max.), 1 PSU expander and 3 I/O expanders (optional)
To access or install an expander:
1. Open the front cover on the enclosure.
2. With an appropriate screwdriver loosen (but do not remove) the top two screws
on the mounting bracket.
3. Gently push the mounting bracket in an upward direction until the screws are
free from contact with the bracket.
4. Slowly but firmly pull the mounting bracket out until it rotates down and is
secured by the resting pins.
5. The underside of the mounting bracket and the enclosure provides space for
additional expanders to be installed (secured by 4 mounting pillars).
See Fig. 8: Rotated views

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Spce652

Tabla de contenido