USER INSTRUCTIONS
1.u - POWER-UP AND NORMAL OPERATION
When switched on, or after a power failure, the appliance assumes non-operating
status
(it does not detect gas) for
one
minute while the sensor warms up (fig. 2).
After one minute the appliance resumes "
Fig. 2 - "Non operating" status
Green LED - alight
!
Yellow LED - blinking
Red LED 1 - off
Red LED 2 - off
Red LED 3 - off
Buzzer - off
Relay - deactivated
(Solenoid valve open)
2.u - INDICATION OF VERY LOW AND LOW GAS
CONCENTRATION
If during normal operation the appliance detects a very low concentration of gas, the
red LED 3 will light up (fig. 4).
If the concentration increases, the red LED 2 will also light up (fig. 5).
Fig. 4 - Very low gas concentration
indicated
Green LED - alight
!
Yellow LED - off
Red LED 1 - off
Red LED 2 - off
Red LED 3 - alight
Buzzer - off
Relay - deactivated
(Solenoid valve open)
normal operating status"
(fig. 3).
Fig. 3 - "Normal operation" status
Green LED - alight
!
Yellow LED - off
Red LED 1 - off
Red LED 2 - off
Red LED 3 - off
Buzzer - off
Relay - deactivated
(Solenoid valve open)
Fig. 5 - Low gas concentration
indicated
Green LED - alight
!
Yellow LED - off
Red LED 1 - off
Red LED 2 - alight
Red LED 3 - alight
Buzzer - off
Relay - deactivated
(Solenoid valve open)
3.u - INDICATION OF GAS WARNING AND GAS ALARM
If the gas concentration in the air exceeds the intervention threshold, the appliance
indicates this situation by activating the red LED 1 alarm and simultaneously emitting an
intermittent buzzer sound (fig. 6).
If the gas presence alarm situation lasts for longer than 15 seconds, the appliance relay is
activated and closes the solenoid valve, if connected (fig. 7).
Fig. 6 - "Gas presence alarm" status
Green LED - alight
!
Yellow LED - off
Red LED 1 - alight
Red LED 2 - alight
Red LED 3 - alight
1s 1s
Buzzer -
1 signal every second
Relay - deactivated
(Solenoid valve open)
WARNING: gas can be smelt in the environment before
the appliance signals alarm.
Main unit in BUS connection only
Fig. 8 - "Gas alarm level from BUS"
status
Green LED - alight
!
Yellow LED - off
Red LED 1 - alight
Red LED 2 - off
Red LED 3 - off
1s 1s
Buzzer -
1 signal every second
Relay - activated
(Solenoid valve closed)
Fig. 7 - "Gas presence alarm" status
and relay activation
Green LED - alight
!
Yellow LED - off
Red LED 1 - alight
Red LED 2 - alight
Red LED 3 - alight
1s 1s
Buzzer -
1 signal every second
Relay - activated
(Solenoid valve closed)
Where several units are BUS
connected, peripheral units in "gas
alarm level" status will transmit a
signal to the main unit, which
switches to "gas alarm level from
BUS" status.
This condition is indicated by red LED
1 only, which remains permanently
alight (Fig. 8).
EN
15