OPL-ADVANTAGE – OPL system
3.2.16 Set reset timer
Use this feature when extra or "stray" signals are present during the final rinse or extract. This will allow for
delaying the reset for up to 75 minutes from the time the load count pump starts.
In the normal mode the reset time starts when the end pump goes on.
In the drain mode the reset time starts when the end pump stops.
When the reset timer activates, it resets the lock-out, the levels and the drain counter.
The programming procedure is the following:
1) Enter access code (see par. 3.2.1) ;
2) Select PUMP "8" and FORMULA "A";
3) Use
to select the time.
4) Press ENTER;
5) The display will briefly flash indicating that the new reset status is set.
6) Press RESET.
3.2.17 Formula enable/disable:
This feature allows the display of only those formula numbers you want visible to the operators. This
prevents the operator from inadvertently choosing an inactive formula. With a new dispenser or after clearing
memory all formula numbers are visible by default.
The programming procedure is the following:
1) Enter access code (see par. 3.2.1) ;
2) Select PUMP "F"; The delay time led should be flashing. If not, press MODE to select delay time.
3) Select the formula to be disabled or enabled.
4) Use
to select 000 "Enable formula" or 001 "Disable formula"
5) Press ENTER;
6) The display will briefly flash indicating that enable or disable has been set.
7) Press RESET.
OPL-ADVANTAGE
Enable
code 0000136607
Disable
rev. 1.6 EN