Circutor SVGm IP54 Manual De Instrucciones página 99

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

SVGm IP54
inets are made up of 2, 3 and 4 69 kvar devices in parallel.
The 134 kvar (SVGm-3WF-134C), 201 kvar (SVGm-3WF-201C) and 268 kvar (SVGm-3WF-268C) cabi-
nets are made up of 2, 3 and 4 67 kvar devices in parallel.
Both the parallel configuration and connection are factory-set.
To connect multiple cabinets in parallel, follow these steps:
1.- Select the cabinet that is to contain the "master" device.
2.- Connect the "master" cabinet. The current transformers are only connected to the "master" cabinet.
3.- Connect the "slave" cabinets.
4.- Connect all of the devices using the communication cables (
Note: The communication cable must be a CAT 5 cable or higher.
Connect the OUT terminal from the final slave device in the "master" cabinet to the IN terminal from
the "master" device of the following cabinet, and the OUT terminal from the final "slave" device in this
cabinet to the IN terminal of the "master" device of the following cabinet, and so on (
Master
ON
R
BUS
3
3
2
2
OUT
OUT
(*)
3
3
2
2
IN
IN
ON
R
BUS
SVGm-xxx-200C
Figure 19: Connecting 3 devices in parallel, using the communication cable (200 A Master SVGm IP54).
5.- Configure the installation in the "master" device (see
6.- Complete the configuration of the slave devices (see
7.- Enable the terminator switch for parallel connection, R
in the other devices.
Instruction Manual
Table 9: Communication cable, devices in parallel.
Communication cable
RJ11 connector
1: Not connected.
2: CAN A
3: CAN B
4: Not connected.
4
1
3 2
ON
R
BUS
3
2
IN
3
2
OUT
(*)
3
2
3
2
IN
OUT
ON
R
BUS
).
Table 9
Pinout
Slave
(*)
3
2
OUT
(*) Connections already included in the cabinets
"7.- CONFIGURATION"
"7.- CONFIGURATION").
in the bus end devices only. Then disable
BUS
).
Figure 19
Slave
ON
R
BUS
3
2
IN
3
2
OUT
3
2
IN
ON
R
BUS
).
99

Publicidad

Capítulos

Tabla de contenido
loading

Tabla de contenido